beautypg.com

Rockwell Automation 1503FC IntelliVAC Contactor Control Module - Series E User Manual

Page 51

background image

A-2

Typical Contactor Drop-out Times

1503-UM053B-EN-P – June 2013

Table A.1 – Typical Contactor Drop-out Time Settings (cont.)

Fuse Rating

Contactor Drop-out Time Setting (msec)

Voltage

Designation

400A

800A

< 5000

20E

50

50

30E

40E

50E

65E

80E

100E

125E

150E

175E

200E

250E

300E

350E

75

400E

100

450E

130

500E

240

600E

240 *

75

750E

200

900E

240 *

2 x 250E

50

2 x 300E

75

2 x 350E

75

2 x 400E

100

2 x 450E

130

2 x 500E

240

2 x 600E

240 *

2 x 750E

2 x 900E

Fuse not suitable for use with contactor.


Note:

The drop-out time is chosen to be equal to or greater than the

intersection of the rated contactor interrupting current and the

fuse melt time curve (except where noted * ).