beautypg.com

Rockwell Automation 1503FC IntelliVAC Contactor Control Module - Series E User Manual

Page 43

background image

Monitoring and Troubleshooting

5-5

1503-UM053B-EN-P – June 2013

Table 5.C - IntelliVAC Status Indication (Series E only)

Conditions



Description

Module Status

Contactor Status

LED Color

Relay

LED Color

Relay

Normal

Healthy Module and Contactor OPEN

Green

Closed

Off

Open

Normal

Healthy Module and Contactor CLOSED

Green

Closed

Yellow

Closed

Warning

Invalid Command Present 

Yellow

Closed

Off

Open

Warning

Mechanical Latch Fail to Trip

Yellow

Closed

Yellow

Closed

Fault

Power Up with Contactor CLOSED

Red – Flash 2 

Open

Yellow

Closed

Warning

Contactor Fails to Pick Up

Yellow – R1 

Closed

Off / Yellow 

Open/Closed 

Warning

Contactor Drop Out During Hold

Yellow – R2 

Closed

Off / Yellow 

Open/Closed 

Warning

Long Contactor Drop Out Time

Yellow – R3 

Closed

Off / Yellow 

Open/Closed 

Fault

Microcontroller Malfunction

Red

Open

Red

Open

Fault

Power Up with Invalid Dip Switch Configuration

Red – Flash 1 ⊂

Open

Off

Open

Fault

Contactor Fails to Drop Out

Red – Flash 3

11

Open

Red

Open

Warning

Undervoltage with a CLOSE Command Present

Yellow – Flashing

Open/Closed  Off / Yellow 

Open/Closed 

Warnings will be cleared when a change of input state occurs, and the condition has been resolved.

Faults require control power to be removed until the unit resets

Flash 1 = 1 Flash Red LED followed by a pause

Flash 2 = 2 Consecutive Red LED flashes followed by a pause

Flash 3 = 3 Consecutive Red LED flashes followed by a pause

Yellow – R1 = Yellow with 1 Red flash followed by a pause

Yellow – R2 = Yellow with 2 consecutive Red flashes followed by a pause

Yellow – R3 = Yellow with 3 consecutive Red flashes followed by a pause

Invalid Command Types:

1. Close, Jog or Trip commands present during power up sequence

2. Close or Jog command re-applied too quickly (before contactor opening sequence is verified).

Allow at least 60 msec, plus drop out delay time, before re-applying these signals.

NOTE: Contactor will only respond to a close command re-applications after the re-start delay timer has expired.

3. Close and Trip commands present simultaneously (valid with Mechanical Latch contactors only).

Open during undervoltage, Closed if voltage restored

Will reflect actual status of the contactor

11