Rockwell Automation 1503FC IntelliVAC Contactor Control Module - Series E User Manual

Page 37

background image

4-2

Setup and Commissioning

1503-UM053B-EN-P – June 2013

An IntelliVAC unit shipped separately from the factory will have a

default configuration per Table 4.A.

Table 4.A – DIP Switch Factory Default Settings

DIP switch SW1

DIP switch SW2

Description

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

Altitude: 0 – 1000m

0

0

1

Drop-out time: 130 msec

0

1

1

Contactor config.: 400A EH

0

0

0

1

TDUV config.: No TDUV

0

Ext. cap TDUV time: 0.2 sec

0

0

Power-Up Safety: Enable

0

IntelliVAC units shipped in a complete MV controller (Bulletin

1500/1900) will be configured to suit the installed application (i.e.
contactor type). The user should verify the settings before energizing the

equipment. Table 4.B defines the settings for each switch.

Table 4.B – IntelliVAC DIP Switch Explanation