Setup and Commissioning

4-3

1503-UM053A-EN-P – September 2008

The altitude compensation by DIP switch settings applies to Series E 400 amp vacuum contactors only. All 800 amp contactors are adapted

for altitude by altering the return springs. 800 amp contactors are to be set for 1 to 1000m (001 DIP setting).

By-pass contactors in MV SMC applications must be set for 50 millisecond drop-out time.