Electrically Held to Mechanical Latch Contactor • Retrofit Instructions

1502-IN001

%-EN-P –-XQH

Auxiliary Contact Assembly Set-Up


1. Clamp the contactor closed from the back of the unit, using a

C-Clamp (or clamping fixture, part no. 80154-149-51).


2. Insert a 0.030” (0.76 mm) feeler gauge between the plastic

auxiliary contact actuator and the steel actuator plate.
(See Figure 8)

Figure 8 – Set-up of the Auxiliary Contact Assembly

3. Slide the assembly fully forward, until the contacts have fully

engaged.

4. Secure the assembly in place by tightening the auxiliary assembly-

retaining bolt.