Profibus troubleshooting procedures, Configuration error mode, Fatal error mode – Rockwell Automation 193-EPRB Profibus Side Mount Module for the E1 Plus Overload Relay User Manual User Manual
Page 28: Network status led
![background image](/manuals/577904/28/background.png)
Publication 193-UM010A-EN-P – January 2008
4-2 Troubleshooting
Configuration Error Mode
In this mode, the E1 Plus PROFIBUS Module’s NETWORK STATUS LED flashes red at 1Hz.
Fatal Error Mode
In Fatal Error Mode, the E1 Plus PROFIBUS Module’s NETWORK STATUS LED turns solid
red. The overload relay continues in this state as long as the device is powered.
The only way to recover from this mode is to power-cycle the module.
PROFIBUS Troubleshooting
Procedures
Network Status LED
The following table identifies possible causes and corrective actions when troubleshooting
PROFIBUS-related failures using the NETWORK STATUS LED.
Error Type
Description
LED State
Configuration Error
Configuration fault or parameter fault
Flashing Red (1Hz)
Error Type
Description
LED State
Fatal
Power-up initialization failure
Solid Red
Fatal communication error
Table 4.4 Troubleshooting using NETWORK STATUS LED
Color
State
Possible Cause
Corrective Action
None
-
1. The E1 Plus PROFIBUS Module is not receiving power at
the PROFIBUS connector.
2. The module is off-line
Check power and PROFIBUS cable connections.
Green
Red
Off
Flashing (once)
Normal operating state; The E1 Plus PROFIBUS Module is
performing internal initialization procedures.
No action required; the Network Status LED flashes
green-red-off during a normal power-up sequence.
Green
Flashing (1Hz)
Normal operating state; E1 Plus PROFIBUS Module is in idle
state.
No action required.
Green
Solid
Normal operating state; the E1 Plus PROFIBUS Module is
on-line.
No action required.
Red
Flashing (1Hz)
1. Configuration fault
2. Parameter fault
Correct the configuration and restart the PROFIBUS master.
Red
Solid
A fatal error has occurred in the module.
Cycle power to the unit and network. If the fault still exists,
replace unit.
Red
Lit 1s then off
Major internal fault
Cycle power to the unit and network. If the fault still exists,
replace unit. If the problem persists, contact technical support.