Data from ib1 slave to interbus master, Control and status word drivecom 20/21 – Rockwell Automation 160IB1 InterBus Communication Module User Manual
Page 23
InterBus Parameter Descriptions and Data Protocol
5–3
Data from IB1 Slave to InterBus
Master
Speed Feedback, displayed by Register 1, is scaled in RPM according
to P66 - [RPM Scaling].
Table 5.B
Control and Status Word
DRIVECOM 20/21
Control and Status word bits are defined as follows (speed control):
Table 5.C
Control Word (Bit definition)
To start the drive, set the control word (Low Byte) from 6 to Fh.
To stop the drive, set the control word (Low Byte) to 6.
To control the drive via Terminal Block (TB3), the Control Word Low
Byte must be set to 06h (state READY TO SWITCH ON).
Table 5.D
Status Word (Bit definition)
* Internal speed reference/feedback is computed in 0.1Hz increments.
Due to rounding issues speeds in RPM may differ.
Resolution error in RPM = P66 * 0.05.
Example: for P66 = 16.6 the possible error is 1 RPM.
Register No. Register (Words)
Description
0
Status Word
According to DRIVECOM 20
1
Speed Feedback
160 Drive Output Frequency (motor RPM)
2
Diagnostics
reserved
Bit No.
DRIVECOM 20 Control
SSC160
0
Switch-on
1 = Switch-on
1
Disable voltage
0 = Disable
2
Fast Stop
0 = Stop
3
Enable Operation
1 = Enabled
4
reserved
5
reserved
6
reserved
7
Reset Fault
0 to 1 Transition = Reset
8 to 15
reserved
Bit No.
DRIVECOM 20 Status
SSC160
0
Ready to switch-on
1 = Ready
1
Switched-on
1 = Switched-on
2
Operation enabled
1 = Enabled
3
Fault
1 = Fault
4
Voltage-disabled
0 = Disabled
5
Fast stop
0 = Stop
6
Switch-on-disabled
1 = Disabled
7
reserved
8
reserved
9
Remote
0 = Local
10
Speed Ref. Reached
1 = Speed Ref. Reached *
11
Speed limited
1 = Speed limited *
12
reserved
13
reserved
14
Reverse Disabled
1 = Reverse Disabled
15
Direction
1 = Reverse (running)