Installation and Wiring

3–5

Wiring the IB1 Ground Terminal

In addition to the ground connections shown in Appendix C of the
160 SSC manual, the ground terminal at the bottom of the IB1
module must be solidly connected (and as short as possible) to the
signal common terminal 3 at TB3 of the 160 SSC drive, as shown in
Figure 3.4:

This connection shall have a cross section of 1.5 mm

2

.

Figure 3.4
IB1 Module Grounding