Resolving problems – Rockwell Automation 160 160SSC CopyCat Keypad User Manual
Page 28

5-2
Troubleshooting
Resolving Problems
Important:
The connector cable, RPA, and Keypad are not repairable.
Description
Cause
Action
Display is blank.
No power to drive (no Ready light).
Verify that the drive is under power.
Connection failure.
Verify that both ends of the connector cable
are secure.
• Faulty connector cable.
• RPA malfunction.
• CopyCat Keypad malfunction.
• Drive malfunction.
Replace components one at a time in this
order until problem is resolved:
• Connector cable
• RPA
• CopyCat Keypad
• Drive
A fault code is displayed.
There is an active fault.
Refer to the 160 SSC™ Variable Speed Drive
(Series C) User Manual, Publication 0160-
5.15, for a complete listing of fault descriptions
and possible problems and corrective actions.
Display remains:
Connection failure.
Verify that both ends of the connector cable
are secure.
Series C drive has incompatible firmware
installed.
Use a Series C drive with firmware version
FRN 7.01 or higher.
Remote Programming Adaptor is installed on
a 160 Series A or B drive.
No Action. The CopyCat Keypad option is not
compatible with 160 Series A and B drives.
• Faulty connector cable.
• RPA malfunction.
• CopyCat Keypad malfunction.
• Drive malfunction.
Replace components one at a time in this
order until problem is resolved:
• Connector cable
• RPA
• CopyCat Keypad
• Drive
Display shows:
CopyCat Keypad is connected to an
incompatible drive.
No Action. The CopyCat Keypad option is
compatible with 160 Series C drives using
firmware version FRN 7.01 or higher.