Short circuit current rating renewal parts – Rockwell Automation 500LG Lighting Contactor (Mechanically and Electrically Held) User Manual
Page 5
![background image](/manuals/577656/5/background.png)
(5)
12 - 24 VDC
500LG-47CM12
24 VAC / 60/50 Hz
500LG-47CM24
110 - 120 VAC / 60/50 Hz
500LG-47CM120
200 - 277 VAC / 60/50 Hz
500LG-47CM277
12 - 24 VDC
500LG-48CM12
24 VAC / 60/50 Hz
500LG-48CM24
110 - 120 VAC / 60/50 Hz
500LG-48CM120
200 - 277 VAC / 60/50 Hz
500LG-48CM277
115 - 120V 60Hz / 110V 50 Hz
500LG-CCKA1
230 - 240V 60Hz / 220V 50 Hz
500LG-CCKA2
265 - 277V 60Hz / 240V 50 Hz
500LG-CCKA3
347 VAC / 60 Hz
500LG-CCKA4
460 - 480V 60Hz / 440V 50 Hz
500LG-CCKA5
575 - 600V 60Hz / 550V 50 Hz
500LG-CCKA6
Power
Poles
1 or 2
#14 - 8
75° C Cu
35
Coil
1 or 2
#18 - 14
60° / 75° C Cu
15
Control
Module
1
#22 - 12
60° / 75° C Cu
5
Auxiliary
Contacts
1 or 2
#22 - 12
60° / 75° C Cu
7 - 12
Single Power Pole
500LG-1PCK
Double Power Pole
500LG-2PCK
1 NO / NC
500LG-141C
2 NO / NC
500LG-142C
Control Module Kit
Power Pole
Coil
2 Wire
Voltage
Component
Cat. No.
3 Wire
Auxiliary Contact
Wire Range AWG
(Solid or Stranded)
Torque
(lb-in)
Component
# of Wire
Wire Temp.
250V
277V
480V
600V
Short Circuit
Current Rating
(amps)
14,000
10,000
5,000
5,000
Class J
Class RK1
Maximum Fuse
100,000
50,000
30
Maximum
Breaker Size
(amps)
30
30
40
40
At AC Service Voltage
600V or less
Available Symmetrical Amperes RMS
Short Circuit Current Rating
Renewal Parts
110 - 120VAC
220 - 240VAC
440 - 480VAC
550 - 600VAC
1
1.5
2
5
5
10
5
15
16
12
12
15.2
14
14
11.2
17
HP
FLA
Maximum horsepower rating(Normal Duty)
1O
3O
1O
3O
1O
3O
1O
3O
PH
Across the line AC
motor starting