Appendix, Interrupt ignore time, Original instructions – Rockwell Automation 440R MSR42 Control Module User Manual User Manual
Page 15
13
MSR42 Control Module User Manual
Original instructions
Appendix
Special MSR42 control module features -- for existing customers.
Interrupt Ignore Time
This function is not included in the standard version.
A limited time a light curtain interruption will be ignored. This may be
used when parts move through the light curtain at high speed and the
safety output should not switch, but yet a person moving through the
light curtain should be detected and cause the safety output to switch off.
Activating this operating mode, a limited time a light curtain
interruption will be ignored. This may be used when parts may move at a
fast speed through the light curtain without interrupting, but a human
will interrupt the light curtain at time longer than the configurated time.
The Interrupt Ignore Time function has to be activated by the MSR42
“Configuration & Diagnostic Tool” software and downloaded to the
MSR42 control module with help of the USB/optical interface (445L-
AF6150)
Start pulse duration
Min.
Max.
50 ms
5s See page 7
Test pulse duration (min.)
response time x 2
Control current into:
GPIO1 – GPIO4
7 mA each at U
N
(coded)
Maximum cable length for safety switches
50 m out and back (total 100 m) See page 6 or 10
Safety Prevention Lamp
Minimum current at Lamp
0.9 A with lamp switched on
GPIO1 – GPIO4 Outputs to safety components
Nominal voltage
U
N
– 2 V (coded)
(Short circuit protected)
Current max
100 mA (short-circuit protected)
Leakage current
I
MAX Off
= 0.05 mA (C
LOAD
= 100 μF)
Info 1, Info 2 Status Outputs (PNP)
Voltage
U
N
– 2 V
Current max
100 mA (short-circuit protected)
Leakage current
I
MAX Off
= 0.05 mA (C
LOAD
= 4.7 μF)
2 OSSD semi conductor outputs (PNP)
Voltage
U
N
- 2 V
Current Max
400 mA
short-circuit protected and with cross-fault
detection
Leakage current
I
MAX Off
= 0.1 mA (C
LOAD
= 3.3 μF)
Max. response time t(C) with UN protective mode
See page 4
≤ 15 ms
Max. response time t(GPIO) with UN protective
mode See page 4
≤ 130 ms
Minimal off time
82 ms
Safety Related Parameter
Probability of a dangerous failure per hour PFH
D
6.0 E-9 1/h
MSR42 & MSR45E & Micro 400
9.0 E-10 1/h
MSR42 & MSR41 Control Module
3.0 E-10 1/h
MSR45E Expander Module
4.0 E-9 1/h
Micro 400 Light Curtain
Performance Level PL
PL e, Cat. 4 (EN ISO 13849-1)
Safety Integrity Level
SIL CL 3 (IEC 61508 / IEC 62061)
Inputs
Interrupt Ignore Time will increase the
response time. The response time is given
in the corresponding configuration
control document. Recalculate the safety
distance.