Quick start guide, Aux# assign – Rockwell Automation 825P Modular Protection System Quick Start Guide User Manual
Page 19
Quick Start Guide
—
Allen-Bradley Bulletin 825-P Modular Protection System
19
19
AUX# Assign
The 825-P allows mapping of protection (trip and warning) and general-purpose
control elements to the auxiliary outputs. Assign functions to the auxiliary relays in
the same manner as performed with the Trip relay settings.
Table G: Auxiliary Relay Functions
Bit
0
1
2
3
4
5
6
7
AUX# A
Overload
Undercurrent
Jam
Current
Imbalance
Short Circuit RTD - W/B
PTC
Ground Fault
(Res)
AUX# B
VAR
Underpower
Under-voltage
Over-voltage
Phase
Reversal
Power Factor
Speed
Switch
Ground Fault
(CB)
AUX# C
Start Time
Freq 1
Freq 2
RTD (Other)
RTD
(Ambient)
PTC Error
RTD Error
MCM Error
AUX# D
Comm Idle
Comm Loss
Remote Trip
Comm Fault
Reserved
Reserved
Reserved
Reserved
AUX# E
Overload
Warn
Undercurrent
Warn
Jam Warn
Curr Imbal
Warn
RTD-W/B
Warn
Pwr Factr Warn Gnd Flt-CB
Warn
Gnd Flt-Res
Warn
AUX# F
VAR Warn
Underpwr Warn Undervolt Warn Overvolt Warn Speed Sw
Warn
Freq 1 Warn
Freq 2 Warn RTD-Othr
Warn
AUX# G
RTD-Amb
Warn
Setting Warn
General Warn
Load Ctl Upper Load Ctl
Lower
Timer 1
Timer 2
Short Ckt
Warn
AUX# H
Stopped State Running State
Starting State
Star Starting
State
Delta
Starting
State
Start Command Network
Control
Reserved
TIP
The AUX# A through AUX# D bytes are used to map trip
functions to the output. The AUX# E through AUX# H
bytes are used to map warning and status functions to the
output.