10000181820 Ver. 01 - November 2012
EFT/B immunity
(Performance Criteria B)
IEC61000-4-4
DLR Ports: +/-3 kV clamp inject at 5 kHz for 5 min
Module and Output Power: +/-3 kV clamp inject at 5 kHz for 5 min
Digital I/O: +/-3 kV clamp inject at 5 kHz for 5 min
Analog I/O: +/-3 kV clamp inject at 5 kHz for 5 min
Earth Ground: +/-3 kV clamp inject at 5 kHz for 5 min
Surge immunity
(Performance Criteria B)
IEC61000-4-5
DLR Ports: +/-2 kV common mode @ 2 ohms
Module and Output Power: +/-2 kV common mode @ 12 ohms; +/-2 kV
differential mode @ 2 ohms
Shielded Digital I/O: +/-2 kV common mode @ 2 ohms
Shielded Analog I/O: +/-2 kV common mode @ 2 ohms
Conducted radiated
immunity
(Performance Criteria A)
DLR Ports, Module Power, Output Power, Digital I/O, and Analog I/O
150 kHz…80 MHz, CDN inject
10V, with 1 kHz sine wave 80% AM
Compliance
Compliance (when
product is marked)
(1)
(1)
See the Product Certification link at
for Declarations of Conformity, Certificates,
and other certification details.
Value
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
EtherNet/IP
ODVA conformance tested to Ethernet/IP specifications.