Rockwell Automation 20P PowerFlex DC Drive - Frame B Pulse Transformer Circuit Board User Manual
Page 16

16
Rockwell Automation Publication 20P-IN009D-EN-P - February 2012
PowerFlex DC Drive Frame B Pulse Transformer Circuit Board
Pulse Transformer Board FIR2-XX Rev. “N” and Higher
Set DIP switches S3 and S4, located at the bottom right corner of the Pulse
Transformer board (see
Figure 1 - on page 5
for location), to the correct settings
based on the appropriate table below.
Table 5 - 230V AC Input Drives
Table 6 - 460V AC Input Drives
XSW1
XI2CA
X3
XP
TR2
TR1
XR
X4
XY
XCD_IO
TO5
TO3
TO6
TO1
TO4
TO2
KGO1
KGO4
KGO2
KGO5
KGO3
KGO6
T5
T3
T6
T1
T2
KG1
KG4
KG2
KG5
KG3
KG6
XCT
C
U
PE
PE1
V
XTA
XM
D
78 79 35 36 75 76 U2 V2
W
S3
S4
1U2 1V2
T4
1
D
79 35 36 75 76 U2 V2
S3
S4
1
Dip switches S3 and S4 are located at
the bottom, right corner of the board.
IMPORTANT
A blank cell below a switch in the following tables indicate that the setting is
“OFF”.
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
HP
DIP Switch S3
DIP Switch S4
S3-1
S3-2
S3-3
S3-4
S3-5
S3-6
S3-7
S3-8
S4-1
S4-2
S4-3
S4-4
S4-5
S4-6
S4-7
S4-8
146
146
119
40
ON
ON
ON
180
180
147
50
ON
ON
ON
ON
218
218
178
60
ON
ON
ON
ON
265
265
217
75
ON
ON
ON
ON
360
360
294
100
ON
ON
ON
434
434
355
125
ON
ON
ON
ON
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
HP
DIP Switch S3
DIP Switch S4
S3-1
S3-2
S3-3
S3-4
S3-5
S3-6
S3-7
S3-8
S4-1
S4-2
S4-3
S4-4
S4-5
S4-6
S4-7
S4-8
167
167
136.4
100
ON
ON
ON
ON
207
207
169.1
125
ON
ON
ON
250
250
204.3
150
ON
ON
ON
ON
330
330
269.6
200
ON
ON
ON
412
412
336.6
250
ON
ON
ON
ON