PowerFlex® DC Drive - Frame B AC Current Transducers

3

Step 2: Remove the
Protective Covers

1. Remove the screws and washers that secure the plastic shields to the

bottom of the drive and remove the shields.

2. Remove the bolts, washers and wiring from the U and V phase AC input

power terminals.

3. Disconnect the DPI cable from the HIM assembly (if present).

4. Loosen, but do not remove, the screws that secure the bottom cover to

the drive, then slide the cover down and off the drive chassis.

Remove screws and shield

Remove screws and shield

U Phase

V Phase

Remove bolts and wiring

Bottom View

=

Disconnect
DPI cable

Tightening torque:
1.5 N•m (13.3 lb•in)