Uitgebreide-groepparameters, Nederlands-10 – Rockwell Automation 22A PowerFlex 4 Quick Start FRN 6.xx User Manual
Page 72
Nederlands-10
Uitgebreide-groepparameters
Nr.
Parameter
Min/Max
Display/Opties
Default
A051
A052
[Sel digit ing 1]
I/O aansluit-
terminal 05
[Sel digit ing 2]
I/O aansluit-
terminal 06
0/26
0 = “Niet gebruikt”
1 = “Acc 2 & dec 2”
2 = “Joggen”
3 = “Fout aux”
4 = “Preset freq”
5 = “Lokaal”
6 = “Comm.poort”
7 = “Fout wissen”
8 = “Ac/dcStpFtws”
9 = “VrlpStp ftws”
10 = “DCInjStpFtws”
11 = “Vooruit jog”
12 = “Achtruit jog”
13 = “Reg 10 V in”
14 = “Reg 20 mA in”
26 = “Anal invert”
4
A055 [Sel relais-uitg]
0/21
0 = “Gereed/fout”
1 = “Op freq”
2 = “Mtr in bedrf”
3 = “Achteruit”
4 = “Motoroverbel”
5 = “Reg acc/dec”
6 = “Te hoge freq”
7 = “Te hg stroom”
8 = “Te hoge DC V”
9 = “Pogingen op”
10 = “Te hg anal V”
20 = “Param reg”
21 = “Nt-hrst fout”
0
A056 [Niv relais-uitg]
0,0/9999
0,1
0,0
A067 [Accel.tijd 2]
0,0/600,0 sec
0,1 sec
20,0 sec
A068 [Decel.tijd 2]
0,1/600,0 sec
0,1 sec
20,0 sec
A069 [Interne freq]
0,0/240,0 Hz
0,1 Hz
60,0 Hz
A070
A071
A072
A073
[Preset freq 0]
(1)
[Preset freq 1]
[Preset freq 2]
[Preset freq 3]
0,0/240,0 Hz
0,1 Hz
0,0 Hz
5,0 Hz
10,0 Hz
20,0 Hz
(1)
Om [Preset freq 0] te activeren stelt u P038 [Snelheidsref] in op optie 4.
A078 [Jog freq]
0,0/[Max frequentie]
0,1 Hz
10,0 Hz
A079 [Jog Accel/Decel]
0,1/600,0 sec
0,1 sec
10,0 sec
A080 [DC remtijd]
0,0/90,0 sec
0,1 sec
0,0 sec
A081 [DC remniveau]
0,0/(A van drive
× 1,8) 0,1 A
A
× 0,05
A082 [Sel DB weerstand]
0/99
0 = Uit
1 = Norm RA wrst
2 = Gn bescherm
3-99 = % van cyclus
0
A083 [% S-kromme]
0/100%
1%
0% (Uit)
A084 [Start boost]
1/14
Instellingen in % van basisspanning.
8
7 (drives van
3,75 kW)
Variabel koppel
Constant koppel
1 = “30,0; VT”
5 = “0,0; geen IR” 10 = “10,0; CT”
2 = “35,0; VT”
6 = “0,0”
11 = “12,5; CT”
3 = “40,0; VT”
7 = “2,5; CT”
12 = “15,0; CT”
4 = “45,0; VT”
8 = “5,0; CT”
13 = “17,5; CT”
9 = “7,5; CT”
14 = “20,0; CT”
A088 [Max spanning]
20/Nominale V
1 VAC
Nominale V
A089 [Stroomgrens 1]
0/(A van drive
× 1,8) 0,1 A
A
× 1,5
A090 [Sel mtr overbel]
0/2
0 = “Geen derate”
1 = “Min derate”
2 = “Max derate”
0
A091 [PWM frequentie]
2,0/16,0 kHz
0,1 kHz
4,0 kHz
A092 [Poging aut hstrt]
0/9
1
0
A093 [Vertr aut hstrt]
0,0/300,0 sec
0,1 sec
1,0 sec
A094 [Start bij powerup]
0/1
0 = “Uit”
1 = "Vrijgegeven”
0
A095 [Achteruit uit]
0/1
0 = “A.uit vrijg”
1 = “A.uit uit”
0
A096 [Vlg strt vrijgeg]
0/1
0 = “Uit”
1 = “Vrijgegeven”
0
A097 [Compensatie]
0/3
0 = “Uit”
1 = “Elektrisch”
2 = “Mechanisch”
3 = “Beide”
1
A098 [Uitsch stroom SW]
0,0/(A van drive
× 2) 0,1 A
0,0 (Uit)
A099 [Procesfactor]
0,1/999,9
0,1
30,0
A100 [Fout wissen]
0/2
0 = “Gereed/Idle”
1 = “Fout reset”
2 = “Buffer wis”
0
A101 [Program vergrend]
0/1
0 = “Ontgrendeld”
1 = “Vergrendeld”
0
A102 [Sel testpunt]
0/FFFF
1 Hex
400
Ingangstoestand van digitale ing 1
(I/O aansluitterminal 05)
Ingangstoestand van digitale ing 2
(I/O aansluitterminal 06)
Frequentiebron Gebruikte parameter Accel/decel (2)
0
0
[Preset freq 0]
[Accel.tijd 1] / [Decel.tijd 1]
1
0
[Preset freq 1]
[Accel.tijd 1] / [Decel.tijd 1]
0
1
[Preset freq 2]
[Accel.tijd 2] / [Decel.tijd 2]
1
1
[Preset freq 3]
[Accel.tijd 2] / [Decel.tijd 2]
(2)
Wanneer een digitale ingang op “Accel 2 en Decel 2” wordt ingesteld, en de ingang actief is, gaat de
ingang aan de instellingen in deze tabel voorbij.
Zie de Gebruikershandleiding van de PowerFlex 4 voor meer informatie over parameters.