Parámetros de grupo avanzados, Español-10 – Rockwell Automation 22A PowerFlex 4 Quick Start FRN 6.xx User Manual
Page 60
Español-10
Parámetros de Grupo Avanzados
No. Parámetro
Mín/Máx
Pantalla /Opciones
Valor
Predeterminado
A051
A052
[Sel. ent digt 1]
Terminales de E/S 05
[Sel. ent digt 2]
Terminal de E/S 06
0/26
0 = “No se usa”
1 = “Acel/Decel 2”
2 = “Avan/impuls”
3 = “Fallo Aux”
4 = “Frec presel”
5 = “Local”
6 = “Puerto Com”
7 = “Borrar Fallo”
8 = “ParoRamp,CF”
9 = “ParInerc,CF”
10 = “ParInjCC,CF”
11 = “ImpulsAvance”
12 = “ImpulsRetroc”
13 = “EntCtrl10V”
14 = “EntCtrl20mA”
26 = “Inver Anlg”
4
A055 [Sel. Sal. Pulsos]
0/21
0 = “Listo/Fallo”
1 = “EnFrecuencia”
2 = “MotorMarcha”
3 = “Retroceso”
4 = “Sobrcarg mtr”
5 = “Reg Ramp”
6 = “Sobre Frec”
7 = “Sobre Cte”
8 = “Sobre V CC”
9 = “AgotReintent”
10 = “Sobre V Anlg”
20 = “ContParám”
21 = “Fallo no rec”
0
A056 [Nivel Sal Pulsos]
0.0/9999
0.1
0.0
A067 [Tiempo acel. 2]
0.0/600.0 segs
0.1 segs
20.0 segs
A068 [Tiempo decel. 2]
0.1/600.0 segs
0.1 segs
20.0 segs
A069 [Frec Interna]
0.0/240.0 Hz
0.1 Hz
60.0 Hz
A070
A071
A072
A073
[Frec presel 0]
( (1)
[Frec presel 1]
[Frec presel 2]
[Frec presel 3]
0.0/240.0 Hz
0.1 Hz
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
(1)
Para activar [Frec presel 0] establezca P038 [Referencia Veloc] en la opción 4.
A078 [Frecuencia test]
0.0/[Frecuencia Máx.] 0.1 Hz
10.0 Hz
A079 [Impulsos Ace/Dec]
0.1/600.0 segs
0.1 segs
10.0 segs
A080 [Tiempo freno CC]
0.0/90.0 segs
0.1 segs
0.0 segs
A081 [Nivel freno CC]
0.0/(Intens. Var
× 1.8) 0.1 Amps
Amps
× 0.05
A082 [Sel resisten FD]
0/99
0 = Inhabilitado
1 = Res RA Norml
2 = SinProtecc
3-99 = CiclTrab %
0
A083 [% curva-S]
0/100%
1%
0% (Inhabilitado)
A084 [Refuer. arranque]
1/14
Ajustes en % de tensión base.
8
7 (Variadores
de 5 HP)
Par Variable
Par Constante
1 = “30.0, VT”
5 = “0.0, no IR” 10 = “10.0, CT”
2 = “35.0, VT”
6 = “0.0”
11 = “12.5, CT”
3 = “40.0, VT”
7 = “2.5, CT”
12 = “15.0, CT”
4 = “45.0, VT”
8 = “5.0, CT”
13 = “17.5, CT”
9 = “7.5, CT”
14 = “20.0, CT”
A088 [Tensión máxima]
20/Volts nomin var.
1 V CA
Volts nomin var.
A089 [Lím. Corriente]
0/(Intens. Var
× 1.8)
0.1 Amps
Amps
× 1.5
A090 [Selec. SC Motor]
0/2
0 = “NoDesclasif”
1 = “DesclasifMín”
2 = “DesclasifMáx”
0
A091 [Frecuencia PWM]
2.0/16.0 kHz
0.1 kHz
4.0 kHz
A092 [Int. rearme auto]
0/9
1
0
A093 [Retrd reinic aut]
0.0/300.0 segs
0.1 segs
1.0 segs
A094 [Inic al encender]
0/1
0 = “Inhabilitado”
1 = “Habilitado”
0
A095 [Inver Deshab.]
0/1
0 = “Rev Habilit”
1 = “Rev Inhabil”
0
A096 [Act. mrch. Vuelo]
0/1
0 = “Inhabilitado”
1 = “Habilitado”
0
A097 [Compensación]
0/3
0 = “Inhabilitado”
1 = “Eléctrico”
2 = “Mecánico”
3 = “Ambos”
1
A098 [Disparo Corr. SW]
0.0/(Intens. Var
× 2)
0.1 Amps
0.0 = (Inhabilitado)
A099 [Factor Proceso]
0.1/999.9
0.1
30.0
A100 [Borrar fallo]
0/2
0 = “Listo/Inactv”
1 = “Restab fallo”
2 = “BorrarBuffer”
0
A101 [Bloqueo Programa]
0/1
0 = “Desbloqueado”
1 = “Bloqueado”
0
A102 [Sel pto. Prueba]
0/FFFF
1 Hex
400
Estado de Entrada de Ent.
Digital 1 (Terminal de E/S 05)
Estado de Entrada de Ent.
Digital 2 (Terminal de E/S 06)
Fuente de
Frecuencia
Parámetro Acel./Decel. utilizado (2)
0
0
[Frec presel 0]
[Tiempo acel. 1] / [Tiempo decel. 1]
1
0
[Frec presel 1]
[Tiempo acel. 1] / [Tiempo decel. 1]
0
1
[Frec presel 2]
[Tiempo acel. 2] / [Tiempo decel. 2]
1
1
[Frec presel 3]
[Tiempo acel. 2] / [Tiempo decel. 2]
(2)
Cuando una entrada digital se establece en “Acel/Decel 2” y la entrada está activa, dicha entrada anula los ajustes en
esta tabla.
Consulte el Manual del Usuario del PowerFlex 4 para más información sobre parámetros.