Vicor PFC MegaPAC-HPEL Power Factor Corrected AC-DC Switchers User Manual
Page 2
![background image](/manuals/574886/2/background.png)
UG:119
vicorpower.com
Applications Engineering: 800 927.9474
Page 2
voltages (total output voltage should not exceed 400 V). The driver is to the left of
the boosters when looking at the output end of the supply. A user-friendly interface
provides control and output sequencing capability (see Page 16 for more information
about this capability), in addition to useful status indicators. Please consult our
Applications Engineering Department if you have other special requirements.
Standard Features
n
Power Factor Correction; 0.99 at 115 Vac, 0.95 at 230 Vac
n
Universal Input: 85 - 264 Vac, 47-500 Hz, or 100 - 380 Vdc
n
Power Outputs:
PFC MegaPAC-EL: 1,600 W at 230 Vac
PFC MegaPAC-HPEL: 2,400 W at 230 Vac
1,200 W at 115 Vac
1,200 W at 115 Vac
n
Outputs:
PFC MegaPAC-EL and HPEL:
Up to 16 outputs
n
Output ripple: 10 mVp-p or 0.15% whichever is greater
n
Fan Cooled
n
Full power to 40°C; half power to 60°C
n
Soft start for limiting inrush current
n
Conducted EMI meets FCC Class A and EN55022 A specifications
(some configurations meet Class B. contact factory)
n
Harmonic Distortion to EN61000-3-2
n
RoHS compliant available
n
Output Sequencing and General Shutdown (General Shutdown refer to Page 17.
Output sequencing refer to Page 28. Consult Applications Engineering for automatic
sequencing circuitry.)
n
Overcurrent protection on all outputs
n
Overvoltage protection on all ConverterPAC outputs
(not applicable with VI-J00 modules)
n
Overtemperature limiting on all ConverterPAC outputs
(not applicable with VI-J00 modules)
n
Size: 3.4”H x 6.0”W x 15.6”L (85,6 mm x 152,4 mm x 396,2 mm)
n
Safety Agency Approvals: CE Mark, cTÜVus, UL
Optional Features
n
DC OK status signal
n
Current Share Boards - see Pages 25 -28
n
Output voltage adjustment range with built-in potentiometer