Signal Ground (J10-10)
Signal Ground (see Figure 4 and Connector Pin Identification below) is an isolated
ground reference for all J10 interfacing signals, and can be used for ConverterPAC
output status signals such as Power Good. This is not the same as Earth Ground on input
power connector J9.

Enable/Disable (J10-1 to J10-8)
The Enable/Disable control pins allow ConverterPAC outputs to be set either on or off.
J10-1 through J10-8 are the control pins for output positions 1 through 8, respectively
(see Figure 5 and Connector Pin Identification above). For DualQPACs, both outputs are
set on or off by the same control pin. In parallel arrays, only the driver ConverterPAC
need be controlled. The Enable/Disable pins must be pulled low to less than 0.7 V with
respect to Signal Ground to disable the outputs. They will sink 10 mA maximum. These
pins should be open circuited or allowed to exceed 4.5 V when enabled. Do not apply
more than 6 V to these inputs at any time. If driven from an electromechanical switch or
relay, a capacitor should be connected to eliminate the effects of switch bounce.

Figure 4.

Interface Connector

J10-9
J10-10
J10-11
J10-12

Vcc +5V, 0.3A

SIGNAL GROUND

AC POWER OK

GEN SHUTDOWN

J10 INTERFACE

J10-1
J10-2
J10-3
J10-4
J10-5
J10-6

J10-7
J10-8

E/D-1
E/D-2
E/D-3
E/D-4
E/D-5
E/D-6

E/D-7
E/D-8

12

11

10

9

8

7

6

5

4

3

2

1

J10

Figure 5.

Enable/Disable and

General Shutdown

PFC MegaPAC-EL

1

10

12

Signal Ground

General Shutdown

Enable/Disable Output 1

J10

1
0

TTL "1" (OFF)

TTL "0" (ON)

9

Vcc

Using external transistors to
drive enable/diable logic