Taf-l perimeter system iom, Ct-taf-l core, Taf-l underfloor perimeter system – Titus TAF-L Perimeter System IOM User Manual
Page 8
8
Installation Manual - TAF-L Perimeter System
TAF-L Perimeter System IOM
Redefine your comfort zone. ™ | www.titus-hvac.com
CT-TAF-L Core
Place the CT-TAF-L cores into the frames with orientation shown in Fig-
ures 7 and 8 below. With this orientation, air deflection will be into the
room and not against the wall.
A maximum of ¾” may by cut to from each core end. Never cut off the
last core support bar! Doing so may result in unsupported core wings
which will not support foot traffic.
ELEVATION VIEW
SECTION G-G
Rigid
Duct
20"X9"
TAF-L-R
RETURN PLENUM
SECTION F-F
TAF-L-R Return Section
F
F
G
TAF-L-V Cooling Section
G
SECTION H-H
TAF-L-V Cooling Section
H
TAF-L-W Heating Section
H
BLOCK
TAF-L-V
COOLING UNIT
ACTUATOR
3/4" COPPER TUBE
TAF-L-W
HEATING UNIT
Figure 8 - Complete Installation
Note: The TAF-L-V is designed so that the tubing which connects the TAF-L-W together runs just beneath the TAF-L-V unit as to avoid tube interference.
Figure 7 - Proper Core Orientation in Frame
TAF-L Underfloor Perimeter System
Room Side
Wall Side