Installation Manual - TAF-L Perimeter System

TAF-L Perimeter System IOM

Redefine your comfort zone. ™ | www.titus-hvac.com

Wall Angle Placement

Attach a 11/4” x 11/4” x 3/16” angle to the wall where the perimeter
diffuser Assembly will be installed. This includes the long span between
columns and the short section along each column.

The angle should be installed level with top of the desired floor tile
height. The angle will carry half the weight of the diffuser assembly.
See Figure 2.

Floor Tile Placement

Install raised floor tiles with a 61/2” space between the edge of the tile
and the wall. The top of the angle needs to be level with the top of the
floor tiles. See Figure 2.

There needs to be an opening of 61/4” (+/-1/8”) between the floor tile
edge and the angle edge. If wall variations result in less than a 1/8”
slot, the angle shall be ground down to within tolerance.

PLAN VIEW

5566.44 (APPROX. DISTANCE BETWEEN COLUMNS)

ELEVATION VIEW

* All dimensions are in inches

Floor Tile

Height

Floor Tile

SECTION A-A

Pedestal

Wall

A

Angle Angle

A

ANGLE

1

1

4

X 1

1

4

X

3

16

6

1

2

Minimal Gap

Angle

Pedestal

Floor Tile

6 1/4" +/- 1/8"

Opening for

Perimeter Grille

Figure 2 - Floor Tile and Angle Placement

TAF-L Underfloor Perimeter System