Installation Manual - TAF-L Perimeter System
TAF-L Perimeter System IOM
Redefine your comfort zone. ™ | www.titus-hvac.com
Wall Angle Placement
Attach a 11/4” x 11/4” x 3/16” angle to the wall where the perimeter
diffuser Assembly will be installed. This includes the long span between
columns and the short section along each column.
The angle should be installed level with top of the desired floor tile
height. The angle will carry half the weight of the diffuser assembly.
See Figure 2.
Floor Tile Placement
Install raised floor tiles with a 61/2” space between the edge of the tile
and the wall. The top of the angle needs to be level with the top of the
floor tiles. See Figure 2.
There needs to be an opening of 61/4” (+/-1/8”) between the floor tile
edge and the angle edge. If wall variations result in less than a 1/8”
slot, the angle shall be ground down to within tolerance.
PLAN VIEW
5566.44 (APPROX. DISTANCE BETWEEN COLUMNS)
ELEVATION VIEW
* All dimensions are in inches
Floor Tile
Height
Floor Tile
SECTION A-A
Pedestal
Wall
A
Angle Angle
A
ANGLE
1
1
4
X 1
1
4
X
3
16
6
1
2
Minimal Gap
Angle
Pedestal
Floor Tile
6 1/4" +/- 1/8"
Opening for
Perimeter Grille
Figure 2 - Floor Tile and Angle Placement
TAF-L Underfloor Perimeter System