CT-TAF-L Blank-off Plate

There will be openings between plenums and between plenum ends
and the CT-TAF-L frame ends. Measure these openings and cut blank-off
plates to fit into these gaps. Be sure and follow the following guidelines
for cutting blank-off plates. See Figure 6.

Blank-off plates must lie below the core support bars and a core support
bar cannot sit on a blank-off support strip. (Core will not sit level and
will rock)

Where possible, have at least 2 support strips per cut section to keep the
blank-off plate from falling into the under floor plenum space.

Leave no more than 3 inches from the edge of a support strip to the edge
of the blank-off plate. Sections longer than 3 inches may cause the plate
to sag and vibrate.

Tabs will sit

on Frame

3" Max

Blank-off Plate

Aperture Installation Notes:

1. Position Plates On Frame And Inside Plenum Ends

2. Measure Open Space Between Plenums

3. Cut And Install Blank-Off Plates

Blank-off Plate

Figure 6 - Aperture Plate & Blank-Off Installation