Installation Manual - TAF-L Perimeter System

TAF-L Perimeter System IOM

Redefine your comfort zone. ™ | www.titus-hvac.com

TAF-L-V Cooling Plenum

Position the actuated TAF-L-V cooling units last. Make the necessary
electrical connections to the actuator (shown on page 8) before placing
the unit in the slot .

Place the TAF-L-V units in the slots such that the aperture plates all actu-
ate in the same direction.

Carpeting

Lay carpeting up to the edge of the floor tile and along the angle. Carpet-
ing will cover the plenum flanges. See Figure 5.

CT-TAF-L Frame

The CT-TAF-L diffuser frame is supplied in multiple sections. Each section
goes into the slot and sits on top of the carpeting.

Place the frame sections into their appropriate positions in the slot. See
Figure 5. A maximum of ½” may be cut off of any ‘Y’ frame end. Align-
ment clips may no longer fit if a section has been cut.

Never cut off the

last frame cross support bar!

See page 5 for alignment clip installation instructions.

Carpet

ELEVATION VIEW

CT-TAF-L Frame

Plenum End Cap

Actuator

SECTION C-C

C

C

Wall

Cove Molding

Carpet

1

2

"

Figure 5 - Carpet & Frame Installation

TAF-L Underfloor Perimeter System