0-25 PSI

GAUGE

L

H

CONTROLLER

0-25 PSI

GAUGE

BULB

SQUEEZE

MAIN AIR (20-25 PSI)

ACTUATOR

BLUE

M

WHITE

YELLOW

T

B

LO

SENSOR

HI

RESET

THERMOSTAT

POINT

START

COLD AIR

DA

RA

HOT AIR

DA

RA

HI

DAMPER

NO

NC

GREEN

LO

INCR

RED

PNEU-IOM-5.0

5-2-05

Reset Start Point Instructions for the TITUS II Controller

Setup Procedure

1.

Confirm the setting on the
Thermostat adjustment Switch for
TITUS II controls.

2.

Confirm the setting on the Damper
Switch.

3.

Disconnect the red HI and green LO
lines from the controller.

4.

Detach the white thermostat line
from Port T on the controller. Attach
a squeeze bulb with 0 to 25 PSI
gauge to Port T.

5.

Remove the yellow motor line from
Port B on the controller. Attach a 0
to 25 PSI gauge to Port B.

To Adjust the Start Point

Direct-Acting Thermostats:

1.

Apply zero PSI to thermostat
Port T.

2.

Adjust the LO knob on the face of
the controller until the gauge on
Port B reads:

2 PSI for normally closed terminals

[or]

15 PSI for normally open terminals.

3.

Use the Squeeze-Bulb to set the
thermostat pressure to 8 PSI or
(whatever PSI the desired setpoint
should be).

4.

Adjust the Reset-Start-Point knob
until the gauge on Port B reads:
(Note 1)

4-5 PSI for normally open terminals

[or]

10-11 PSI for normally closed terminals.

5.

SEE NOTE 2.

Reverse-Acting Thermostats:

1.

Apply 15 PSI to thermostat Port T.

2.

Adjust the LO knob on the face of
the controller until the gauge on
Port B reads:

2 PSI for normally closed terminals

[or]

15 PSI for normally open terminals.

3.

Use the Squeeze-Bulb to set
thermostat to desired start-point
PSI.

4.

Adjust the Reset-Start-Point knob
until the gauge on Port B reads:
(Note 1)

4-5 PSI for normally open terminals

[or]

10-11 PSI for normally closed terminals.

5.

SEE NOTE 2.

NOTE 1: Pressures shown are for

5-10 PSI actuators. For other
spring ranges adjust readings
accordingly.

NOTE 2: Reconnect Red-Green-

Yellow-White tubes to their
proper control terminals.

Recalibrate Min./Max. CFM
settings in accordance with
procedures shown in the proper
Installation Manual.

Figure 7. Titus II Controller