beautypg.com

Titus Pneumatic Controls IOM User Manual

Page 3

background image

ACTUATOR

SENSOR

(0-20" WG)

GAUGE

MAGNAHELIC

H

L

HI

LO

X

(0-15 PSI)

MAIN AIR (20-25 PSI)

ROOM THERMOSTAT

WHITE

YELLOW

BLUE

T

M

Y

B

GREEN

RED

HI

LO

HI

REVERSE ACTING CONTROLLER

DIRECT ACTING CONTROLLER

INCREASE

GRAY

HI

INCREASE

LO

LO

HI

BEIGE

INCREASE

HI

LO

LO

INCREASE

LO

PNEU-IOM-3.0

5-2-05

Calibration Procedure for TITUS I Controller

A.

Direct Acting (Beige). (N.O.)

1.

Adjusting minimum air flow:
a.

Apply zero PSI signal to Port T
on the controller.

b.

If the minimum CFM equals
zero, the damper should
assume

a

closed

position (observe the indicator
on the end of the damper
shaft). If not, adjust LO knob on
the controller until the
compressed air drives the
damper closed.

c.

If a non-zero minimum CFM is
required, read the differential
pressure for the desired CFM
from the calibration curve
corresponding to the inlet size
of the terminal being calibrated
(Page 8).

d.

Adjust the LO knob until the
desired differential pressure is
read on the manometer gauge.
Allow several seconds for the
controls to react to system
pressure and stabilize.

2.

Adjusting maximum air flow:
a.

Apply 15-25 PSI signal to
Port T on the controller.

b.

Refer again to the calibration
curve (Page 8) to determine
the differential pressure
necessary for the required
maximum CFM.

c.

Adjust the HI knob on the
controller until the manometer
gauge reads the required
differential pressure from the
curve.

NOTE: If actuator fails to respond,
see Guide to Service Procedure.

B.

Reverse Acting (Gray). (N.C.)

1.

Adjusting maximum air flow:
a.

Apply zero PSI signal to Port T
on the controller.

b.

Refer to calibration chart (Page
8). Read the differential
pressure for the desired
maximum CFM from the curve
corresponding to the inlet size
of the terminal being
calibrated.

c.

Adjust the HI knob on the
controller until the desired
differential pressure is read on

the manometer gauge. Allow
several seconds for the
controls to react to the system
and stabilize.

2. Adjusting

minimum air flow:

a.

Apply 15-25 PSI signal to
Port T on the controller.

b.

If minimum CFM equals zero,
the damper should assume a
closed position (observe
indicator on the end of the
damper shaft). If not, adjust the
LO knob until the damper
closes.

c.

If a non-zero minimum CFM is
required, read the differential
pressure for the required CFM
from the curve (Page 8).

d.

Adjust the LO knob on the
controller until the manometer
gauge reads the desired
differential pressure from the
curve.

NOTE: If actuator fails to respond,
see Guide to Service Procedures.

Thermostat

Action

Color

Low Port Signal

High Port

Signal

Direct

Beige

Y

X

Reverse

Grey

X

Y

Table 1.

Figure 5. Titus I Controller