beautypg.com

Rab installation manual, Motorized air damper – Titus RAB IOM User Manual

Page 6

background image

RAB Installation Manual

IOM-RAB-00

08-15-04

6 of 10

Installation

1. Remove end return air panel and discard. See

Figure 7.

2. Attach side frame rails using sheet metal screws as

provided (size 10 x ¾-inch with bonded-seal

washers).

3. Attach top frame rail using sheet metal screws as

provided.

4. Attach bottom frame rail using sheet metal screws

as provided.

5. Attach manual outside air damper, intake hood, and

filter assembly.

Motorized Air Damper

The motorized outside air damper kit can be used only

with the manual air damper. The motor kit components

consist of the motor operator, hood assembly, hardware

(fasteners and screws), and installation instructions.

Figure 8 shows the motor placement onto a manual

operation air damper.
Only qualified and trained HVAC technicians should install

the motorized outside air damper kit.
The instructions serve as guidelines to the technician

installing the kit.

Preparation

Upon receipt of materials, check shipping container

for damage. If damaged, contact shipping carrier.

Unpack the motor assembly that includes the motor

operator, operator hood assembly, and instructions.

Sort contents, especially fasteners, nuts, and bolts

according to size and type.

Figure 8. Air Damper Motor Placement onto

Damper Shaft

DANGER

ELECTRIC SHOCK CAN CAUSE DEATH.

Caution: Disconnect all power supplies before

accessing equipment.
Disconnecting more than one power supply may

be required to de-energize some equipment.
Allow all rotating parts to completely stop before

attempting damper motor kit installation.

Installation

1.

Remove filter from bottom of the fresh air intake.

2.

Remove handle from the outside of the fresh air

intake. Damper rod should extend beyond unit

exterior.

3.

Position damper blade to its fully closed position.

4.

Press manual override button and rotate actuator

clamp to about 1/16 and 1/8-inch between actuator

stop and clamp.

5.

Slide actuator over damper rod and finger-tighten

nuts.

6.

Slide anti-rotation bracket (L-bracket) up and under

actuator engaging center cutout on actuator back,

see Figure 9.

Figure 9. Mounting Bracket Placement