RAB Installation Manual

IOM-RAB-00

08-15-04

3 of 10

Table 2. Service Data

Water Coil Connection Size (inches)

Model

Nominal

Capacity

Nominal

CFM

Coil Free

Area

(Sq. Ft.)

4-Row

6-Row

2-Row

Filter Size

(inches)

RAB08

2

800

2.0

¾

¾

5/8

16 x 32

RAB12

3

1200

3.0

¾

7/8

7/8

16 x 32

RAB16

4

1600

4.0

7/8

1-1/8

7/8

(2) 20 x 20

RAB20

5

2000

5.0

1-1/8

1-1/8

1-1/8

(2) 20 x 20

RAB30

7.5

3000

8.1

1-3/8

1-5/8

1-1/8

(2) 16 x 20
(2) 16 x 25

RAB40

10

4000

9.5

1-3/8

1-5/8

1-1/8

(2) 16 x 20
(2) 16 x 25

RAB60

15

6000

12.8

1-3/8

1-5/8

1-3/8

(3) 16 x 20
(3) 16 x 25

RAB80

20

8000

17.5

1-3/8

1-5/8

1-18

(4) 16 x 20
(4) 16 x 25

Note: All water coil connection sizes are outside diameter (OD) sweat (SWT) dimensions.

Table 3. Shipping Weights

Shipping Weight (lbs.)

Model 2-Row

Coil

4-Row

Unit

6-Row

Unit

Modulating

Damper

Roof

Curb Kit

Manual

Damper

Horizontal

Modulating

Damper

RAB08

13

280

290

90

85

50

120

RAB12

18

280

290

90

85

50

120

RAB16

25

315

340

135

95

95

220

RAB20

30

410

420

135

95

95

220

RAB30

40

540

550

175

105

125

300

RAB40

45

580

590

175

105

125

300

RAB60

55

745

760

180

105

125

315

RAB80

75

950

970

200

120

145

410

Installation

Basic installation procedure covers verifying and/or

installing the following items.

Ductwork

Duct insulation and vapor proofing

Unit placement

Sound attenuation

Condensate drain

Water piping

Motors and drives

Electrical connections

Ductwork

Use accepted industry practices and design guidelines of

the ASHRAE Fundamentals Handbook. Ductwork must

comply with all building codes and the NFPA pamphlet

90A and 90B.
Carefully inspect any previously installed ductwork to

determine suitability.

Note: Ductwork should be of a size meeting

requirements of the installation. Ductwork should

transition gradually from a smaller size blower outlet

to required duct run size to avoid excessive loss of

air velocity.