Adjusting Minimum and Maximum Air Flow for Units with Hot Inlet Sensor and Cold Discharge
Sensor

A. Direct Acting Thermostat Air

Flow Adjustment

1.

Hot inlet controller. Be sure the hot
inlet damper assumes a fully closed
position during cooling conditions.
Apply 15-25 PSI pressure to the
thermostat connection of the hot
inlet controller. If the hot inlet
damper does not fully close, adjust
LO air flow know until the damper
closes. Allow several seconds for
the controls to react to system
pressure and stabilize.

To adjust hot deck maximum CFM:

a.

A p p l y z e r o P S I t o t h e
thermostat connection on the
hot deck controller. Place a
manometer gauge across the
balancing tees at the hot deck
inlet.

b.

I f t h e m a n o m e t e r g a u g e
reading matches the required
differential pressure from the
calibration curve (Page 6 and
7 ) , n o a d j u s t m e n t i s
necessary.

c.

If adjustment is necessary, use
the adjusting tool stored in the
face of the controller (Titus II
only) or a standard flat-blade
screwdriver.

d.

Rotate the maximum HI knob
slowly. A delay in response
time has been deliberately built
i n t o t h e c o n t r o l s t o a v o i d
hunting. Allow several seconds
from controls to react and the
system to stabilize. Rotate the
know until the gauge shows the
required differential pressure.

N O T E : I f t h e a c t u a t o r f a i l s t o
r e s p o n d , s e e G u i d e t o S e r v i c e
Procedures.

T o a d j u s t M i n . / M i x C F M o n c o l d
controller / discharge sensor:

a.

Apply 8.0 PSI pressure to the
thermostat connection of the
cold deck controller.

b. If Min./Mix CFM equals zero.

The cold inlet damper should
assume a closed position. If
not, adjust minimum LO knob
on the cold inlet controller until
the damper closes.

c.

If Min./Mix CFM is a non-zero
value, place a mano m e t e r
gauge across the balancing
tees of the cold deck inlet. If
the p r e s s u r e m a t c h e s t h e
required differential from the
calibration curve (Page 6 and
7), no adjustment is necessary.

d.

If adjustment is necessary,
rotate the minimum LO knob
until the gauge s h o ws t h e
required differential pressure.

To adjust cold deck maximum CFM:

a.

Apply 15-25 PSI pressure to
the cold deck controller. Place
a manometer gauge across the
balancing tees at the cold deck
inlet.

b.

I f t h e m a n o m e t e r g a u g e
reading matches the required
differential from the calibration
c u r v e ( P a g e 6 a n d 7 ) , n o
adjustment is necessary.

c.

If adjustment is necessary,
rotate the maximum HI knob
slowly. Rotate the knob until
the gauge reads the required
differential pressure from the
curve.

Figure 3. Variable Air Volume
Piping Diagram

Figure 4. Constant Air Volume
Piping Diagram

T

M

ACTUATOR

ACTUATOR

CONTROLLER

T

M

B Hi

LO

Hot

Cold

CONTROLLER

M

Lo

T

Hi

B

START

POINT

THERMOSTAT

COLD AIR

HOT AIR

DA

DA

RA

RA

NC

NO

DAMPER

RESET

LO

HI

INCR

Adjustment Tool

Table 1. Thermostat Switch Settings

Figure 5. Titus II Controller

DA/Cold RA/Hot

8-13 PSI Reset Span
0-8 PSI Min CFM / LO Dial
13-25 PSI Max CFM / HI Dial

RA/Cold DA/Hot

3-8 PSI Reset Span
0-3 PSI Max CFM / HI Dial
8-25 PSI Min CFM / LO Dial