beautypg.com

Mab installation manual, Installation of options, Motors and drives – Titus MAB IOM User Manual

Page 6: Electrical connections, Grille plenum

background image

MAB Installation Manual

IOM-MAB-00

08-15-04

6 of 9

Motors and Drives

Units are normally shipped with motor and drive installed.

However; when mounting a motor on the adjustable base

in the field, use extreme care to ensure proper alignment

and belt tension.

Electrical Connections

Each unit has a mounted control box, and typically, the

motor is to be wired to this box. Only ODP, single- and

three-phase motors on 800 to 2000 CFM units are factory-

wired to junction box. All other motors require field wiring

to junction box located on side of the unit cabinet.

Note 1: Unit must be permanently grounded in

accordance with NEC and local codes and

ordinances. See the typical wiring diagrams shown in

Figure 7.
Note 2: Not all installations require a starter (some

motors utilize a contactor).

Figure 7. Wiring Diagrams

Installation of Options

In addition to the standard equipment, the following

optional equipment may require consideration during

installation.

Discharge grille plenum.

Mixing box.

Electric heat.

Motor and drive selections.

Grille Plenum

The discharge grille plenum is designed for a freestanding

configuration set in an open area with a requirement for a

90° turn of the discharge air. See Figure 8. This option is

available on models MAB16 through 80.
1.

Check plenum alignment with unit. Remove screws

aligning with the smaller plenum cutouts. Retain

screws for later.

Note: Screws aligning with the larger cutouts

remain in place.

2.

Remove grille from the plenum.

3.

Position plenum so discharge is directed toward

the back or front of unit, as desired.

4.

Align the ½-inch holes in the plenum with the unit’s

protruding screw heads.

5.

Align the smaller ¼-inch holes in plenum and unit

together.

6.

Square up plenum and unit; then reach through

grille opening to insert screws into the smaller ¼-

inch holes.

7.

Tighten all screws to secure plenum.

8.

Reinsert grille in plenum opening and secure with

screws retained previously. Adjust grille louvers

manually.

Figure 8. Grille Plenum Installation