Face and bypass damper add-on filter section, Startup, Hab installation manual – Titus HAB Horizontal Air Handler Belt Drive User Manual
Page 8

HAB Installation Manual
IOM-HAB-00
06-30-04
Figure 13. Electric Heat Installation
Face and Bypass Damper Add-on Filter
Section
HAB units equipped with face and bypass damper
s may have
the add-on filter section specified as an option. Add-on filter
sections ship separately and are field installed. Figure 14
shows the add-on filter section placement. Use the following
steps as guidelines for filter section installation.
1. Slip add-on filter section over the face and bypass
damper front.
2. Secure filter section to damper using field-supplied short
sheet-metal screws inserted into factory-punched holes.
3. Verify screws do not hinder damper operation.
Startup
Check the following items before startup.
•
Ensure all shipping bolts/screws are removed and all
other bolts and screws are tight.
Figure 14. HAB Model with Bypass Damper
and Add-on Filter Section
−
Not all installations require a starter (some
motors utilize a contactor).
•
Ensure all filters are installed. Perform filter check
with all doors and panels in place.
•
Never assume the voltage and phase on the unit
nameplate is the same was the motor wired.
•
Check alignment of the sheaves and ensure the
setscrews are tight.
•
Check for proper rotation of the blower pulley.
•
Check motor phase and rotation.
−
Exchanging two of the three leads at the unit
junction box.
−
Exchanging leads inside the motor junction box can
reverse the rotation of single-phase motors. Refer to
the motor nameplate.
•
Check amperage draw of the motor. The
amperage draw should not exceed the nameplate
amps shown on the motor serial plate.