Figure 13. Electric Heat Installation

Face and Bypass Damper Add-on Filter

Section

HAB units equipped with face and bypass damper

s may have

the add-on filter section specified as an option. Add-on filter

sections ship separately and are field installed. Figure 14

shows the add-on filter section placement. Use the following

steps as guidelines for filter section installation.
1. Slip add-on filter section over the face and bypass

damper front.

2. Secure filter section to damper using field-supplied short

sheet-metal screws inserted into factory-punched holes.

3. Verify screws do not hinder damper operation.

Startup

Check the following items before startup.

Ensure all shipping bolts/screws are removed and all

other bolts and screws are tight.

Figure 14. HAB Model with Bypass Damper

and Add-on Filter Section

Not all installations require a starter (some

motors utilize a contactor).

Ensure all filters are installed. Perform filter check

with all doors and panels in place.

Never assume the voltage and phase on the unit

nameplate is the same was the motor wired.

Check alignment of the sheaves and ensure the

setscrews are tight.

Check for proper rotation of the blower pulley.

Check motor phase and rotation.

Exchanging two of the three leads at the unit

junction box.

Exchanging leads inside the motor junction box can

reverse the rotation of single-phase motors. Refer to

the motor nameplate.

Check amperage draw of the motor. The

amperage draw should not exceed the nameplate

amps shown on the motor serial plate.