PERFORMANCE DATA (cont)
ELECTRIC HEATING CAPACITIES
ELECTRIC HEATING CAPACITIES (cont)
*Two heater packages required to provide kW indicated.
†On units with factory-installed outlet, use CRSINGLE014A00.
NOTES: The kW ratings shown above are at 240 and 480 v. Use the Multiplication
Factors table to determine heater capacity for your particular voltage.
MULTIPLICATION FACTORS
EXAMPLE:
32.0 kW (at 240 v) heater on 208 v
= 32.0 (.75 mult factor)
= 24.0 kW capacity at 208 v.
OUTDOOR SOUND POWER (TOTAL UNIT)
UNIT
549B
VOLTAGE
(60 Hz)
ACCESSORY
kW
ACCESSORY
HEATER
PART NUMBER
CRHEATER---A00
ACCESSORY
SINGLE
POINT BOX
PART NO.
CRSINGLE---A00
036
208/230
(single phase)
4.4
101
—
6.5
102
—
8.7
103
—
10.5
104
—
13.0*
102*
004
208/230
(3 phase)
4.4
101
—
6.5
102
—
8.7
103
—
10.5
104
—
16.0
105
—
460
(3 phase)
6.0
106
—
8.8
107
—
11.5
108
—
14.0
109
—
048
208/230
(single phase)
4.4
101
—
8.7
103
—
13.0*
102*
004
17.4*
103*
004
21.0*
104*
004
208/230
(3 phase)
6.5
102
—
8.7
103
—
16.0
105
—
21.0*
104*
002
460
(3 phase)
6.0
106
—
11.5
108
—
14.0
109
—
23.0*
108*
—
060
208/230
(single phase)
6.5
102
—
8.7
103
—
13.0*
102*
004
17.4*
103*
004
21.0*
104*
004
208/230
(3 phase)
6.5
102
—
10.5
104
—
16.0
105
—
21.0*
104*
002
26.5*
105,104
002
460
(3 phase)
6.0
106
—
11.5
108
—
14.0
109
—
23.0*
108*
—
25.5*
109,108
—
072
208/230
(3 phase)
6.5
102
—
10.5
104
—
16.0
105
—
21.0*
104*
002
26.5*
105,104
002
460
(3 phase)
6.0
106
—
11.5
108
—
14.0
109
—
23.0*
108*
—
25.5*
109,108
—
UNIT
549B
VOLTAGE
(60 Hz)
ACCESSORY
kW
ACCESSORY
HEATER
PART NUMBER
CRHEATER---A00
ACCESSORY
SINGLE
POINT BOX
PART NO.
CRSINGLE---A00
090
208/230
(3 phase)
10.4
117
006
16.0
110
006
24.8
111
007
32.0
112
007
42.4*
112,117
009
460
(3 phase)
13.9
116
006
16.5
113
006
27.8
114
006
33.0
115
006
41.7*
114,116
008
120
208/230
(3 phase)
10.4
117
012
16.0
110
012
32.0
112
012
42.4*
112,117
015
50.0*
112,110
015
460
(3 phase)
16.5
113
011
27.8
114
011
33.0
115
011†
41.7*
114,116
014
50.0*
115,113
014
HEATER kW
RATING
VOLTAGE
DISTRIBUTION
V/3/60
MULTIPLICATION
FACTOR
240
200
.69
208
.75
230
.92
240
1.00
480
440
.84
460
.92
480
1.00
549B
ARI
RATING
(dB)
OCTAVE BANDS; Lw (A)
63
125
250
500
1000
2000
4000
8000
036,048
76
50.8
63.4
62.2
65.9
69.2
65.9
63.0
56.5
060,072
80
57.6
70.2
66.9
71.7
74.7
72.2
67.8
62.4
090
82
62.3
69.3
71.5
74.7
76.2
72.9
68.7
61.5
120
84
64.6
71.1
73.3
76.9
77.6
73.7
70.6
63.7
ARI
— Air Conditioning and Refrigeration Institute
Lw (A) — Unit A — Weighted Sound Power Level
50
T
F
Q
0
04
-0
12
5
49B
036
-120