PERFORMANCE DATA

COOLING CAPACITIES

548F036 (3 TONS)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

900/0.10

1200/0.15

1500/0.21

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

42.4

39.9

36.5

43.0

41.2

38.7

45.1

42.8

40.3

SHC

16.7

22.0

26.8

17.5

24.2

30.9

19.3

26.9

34.1

kW

2.77

2.71

2.62

2.78

2.74

2.68

2.85

2.79

2.73

85

TC

41.5

38.4

34.8

43.3

40.4

37.0

44.0

41.7

38.7

SHC

16.6

21.6

26.2

18.2

24.6

30.3

19.3

27.2

33.7

kW

3.01

2.92

2.80

3.07

2.98

2.88

3.09

3.03

2.94

95

TC

40.0

36.3

33.0

42.3

38.5

35.2

43.4

40.0

36.7

SHC

16.2

20.9

25.7

18.2

24.2

29.8

19.7

27.2

32.7

kW

3.24

3.10

2.99

3.32

3.19

3.07

3.36

3.24

3.13

105

TC

38.4

34.7

31.0

40.0

36.7

33.1

41.2

37.7

35.2

SHC

15.7

20.5

24.8

17.5

23.9

28.8

19.3

26.6

31.7

kW

3.47

3.32

3.16

3.53

3.41

3.26

3.58

3.44

3.35

115

TC

36.1

32.5

28.9

38.1

34.3

31.1

39.3

35.5

33.2

SHC

15.1

19.8

23.9

17.2

23.2

27.8

19.1

26.2

30.2

kW

3.66

3.50

3.32

3.76

3.59

3.44

3.81

3.65

3.54

125

TC

34.2

30.5

26.8

35.9

32.0

29.3

36.8

33.0

31.3

SHC

14.6

19.2

22.9

16.7

22.6

26.3

18.5

25.5

28.4

kW

3.88

3.68

3.49

3.97

3.77

3.62

4.02

3.83

3.74

548F048 (4 TONS)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

1200/0.11

1600/0.15

2000/0.22

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

55.5

51.9

47.4

56.9

54.6

50.3

59.3

56.5

52.1

SHC

24.5

31.2

37.4

26.0

35.2

43.4

28.4

39.0

47.6

kW

3.80

3.70

3.55

3.84

3.79

3.66

3.93

3.86

3.71

85

TC

53.4

49.7

45.3

56.3

52.6

47.8

57.5

54.1

49.8

SHC

23.8

30.4

36.7

26.3

34.9

42.6

28.3

38.6

46.9

kW

4.10

3.99

3.84

4.23

4.11

3.94

4.27

4.16

4.01

95

TC

52.0

47.4

43.0

53.7

49.9

45.5

54.5

51.6

47.4

SHC

23.4

29.6

35.8

25.5

33.9

41.6

27.3

38.2

45.2

kW

4.47

4.28

4.11

4.53

4.39

4.23

4.56

4.48

4.29

105

TC

49.3

45.0

40.6

51.8

47.2

43.0

52.6

48.7

45.4

SHC

22.5

28.8

34.7

25.3

33.0

40.3

27.1

37.1

43.3

kW

4.77

4.59

4.39

4.90

4.68

4.52

4.92

4.76

4.63

115

TC

46.6

42.4

38.0

48.8

44.6

40.6

50.2

45.8

43.2

SHC

21.7

27.9

33.6

24.3

32.4

38.7

26.8

36.1

41.2

kW

5.08

4.90

4.66

5.21

5.01

4.81

5.29

5.06

4.96

125

TC

44.0

39.6

35.4

45.6

41.6

38.3

47.0

42.9

40.9

SHC

20.9

26.9

32.4

23.3

31.6

36.5

25.9

35.6

39.0

kW

5.45

5.21

4.96

5.51

5.34

5.14

5.60

5.41

5.30

548F060 (5 TONS)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

1500/0.05

2000/0.08

2500/0.14

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

69.3

64.5

59.3

70.8

67.9

62.8

72.9

69.3

65.4

SHC

30.9

39.2

47.4

33.1

44.9

55.4

35.8

49.4

61.4

kW

4.28

4.15

4.03

4.32

4.25

4.12

4.38

4.29

4.19

85

TC

67.7

62.4

56.8

69.1

65.7

60.2

71.1

67.7

63.2

SHC

30.4

38.6

46.5

32.8

44.6

54.4

35.8

50.0

59.8

kW

4.76

4.61

4.49

4.79

4.72

4.56

4.86

4.78

4.65

95

TC

65.2

59.8

54.4

67.7

62.9

57.6

69.1

64.8

60.7

SHC

29.6

37.6

45.5

32.8

43.6

53.2

35.6

49.3

57.7

kW

5.27

5.10

4.97

5.35

5.20

5.07

5.39

5.27

5.14

105

TC

62.3

57.2

51.8

65.1

59.6

54.9

66.8

61.7

58.3

SHC

28.6

33.8

44.4

32.1

42.6

51.6

35.4

48.2

55.5

kW

5.79

5.66

5.50

5.90

5.73

5.61

5.97

5.79

5.68

115

TC

59.7

54.2

49.0

61.7

57.0

52.5

63.2

58.4

55.8

SHC

27.6

35.8

43.2

31.1

41.9

49.6

34.3

47.0

53.2

kW

6.37

6.24

6.06

6.47

6.34

6.20

6.53

6.36

6.31

125

TC

56.5

51.0

46.0

58.2

53.5

49.8

59.4

55.1

53.0

SHC

26.8

34.7

41.9

30.0

40.8

47.3

33.0

46.5

50.5

kW

7.03

6.87

6.65

7.07

6.96

6.82

7.13

7.03

6.96

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not

extrapolate.

2. The following formulas may be used:

t

lwb

= Wet-bulb temperature corresponding

to enthalpy of air leaving indoor coil
(h

lwb

)

Where: h

ewb

= Enthalpy of air entering evap-

orator coil

3. The SHC is based on 80 F edb temperature

of air entering indoor coil.
Below 80 F edb, subtract (corr factor x cfm)
from SHC.
Above 80 F edb, add (corr factor x cfm) to
SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x
(edb – 80).

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

Ldb — Leaving Dry-Bulb
Lwb — Leaving Wet-Bulb
SHC — Sensible Heat Capacity

(1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR

DRY-BULB TEMP (F)

79

78

77

76

75

under

75

81

82

83

84

85

over

85

Correction Factor

.05

1.04 2.07 3.11 4.14 5.18

Use

formula

shown
below.

.10

.98 1.96 2.94 3.92 4.90

.20

.87 1.74 2.62 3.49 4.36

.30

.76 1.53 2.29 3.05 3.82

50

T

F

Q

0

04

-0

12

5

48F

036

-1

20