beautypg.com

75 performance data, Cooling capacities – Bryant 548F User Manual

Page 75

background image

75

PERFORMANCE DATA

COOLING CAPACITIES

549B036 (3 Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/Bf

900/0.13

1200/0.17

1500/0.19

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

41.7

38.4

34.1

43.2

40.3

37.3

44.4

41.4

36.8

SHC

20.3

25.0

29.0

21.9

28.0

33.7

23.2

30.6

36.8

kW

2.22

2.17

2.13

2.23

2.20

2.17

2.25

2.21

2.18

85

TC

40.5

37.2

32.4

42.1

39.0

36.0

43.1

40.2

37.2

SHC

19.9

24.6

28.1

21.6

27.8

33.2

23.1

30.5

36.3

kW

2.49

2.45

2.40

2.51

2.48

2.44

2.53

2.49

2.45

95

TC

39.1

35.9

30.6

40.8

37.6

33.9

42.0

38.7

35.8

SHC

19.4

24.1

27.2

21.2

27.4

32.2

23.0

30.2

35.8

kW

2.80

2.75

2.69

2.82

2.78

2.74

2.85

2.80

2.76

105

TC

37.6

33.9

28.8

39.2

36.0

32.3

40.1

37.0

34.6

SHC

18.8

23.3

26.3

20.8

26.8

31.4

22.3

29.7

34.5

kW

3.13

3.08

3.01

3.16

3.11

3.06

3.18

3.13

3.09

115

TC

35.9

31.9

27.9

37.4

34.2

30.2

38.3

35.3

32.5

SHC

18.2

22.5

25.8

20.2

26.1

30.1

21.8

29.0

32.5

kW

3.49

3.43

3.36

3.52

3.47

3.40

3.54

3.50

3.45

125

TC

34.2

30.5

26.3

35.5

32.1

28.6

36.3

33.2

31.0

SHC

17.6

21.9

25.0

19.5

25.3

28.6

21.4

28.2

31.0

kW

3.88

3.81

3.74

3.91

3.85

3.79

3.92

3.88

3.84

549B048 (4 Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/Bf

1200/0.13

1600/0.16

2000/0.19

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

53.1

48.7

45.0

55.6

49.6

46.7

56.1

50.7

48.4

SHC

25.1

30.7

36.7

27.3

32.6

40.5

28.2

35.1

44.6

kW

2.92

2.86

2.82

2.96

2.87

2.84

2.96

2.88

2.87

85

TC

51.9

47.3

43.7

53.9

49.1

45.6

54.4

50.2

46.9

SHC

24.9

30.2

36.2

26.7

33.4

40.4

27.7

36.1

44.2

kW

3.29

3.22

3.19

3.32

3.25

3.21

3.32

3.27

3.23

95

TC

50.5

45.5

42.1

51.8

47.4

44.0

52.3

47.4

44.6

SHC

24.3

29.5

35.6

26.0

32.8

39.9

27.0

34.3

42.4

kW

3.70

3.62

3.58

3.71

3.65

3.61

3.72

3.64

3.61

105

TC

48.2

43.7

40.5

50.0

45.3

42.2

50.8

46.3

43.2

SHC

23.6

28.9

35.1

25.7

32.0

39.5

27.2

34.8

42.4

kW

4.14

4.06

4.04

4.16

4.08

4.05

4.18

4.10

4.06

115

TC

45.1

42.1

38.2

46.4

43.5

39.9

46.0

44.4

41.3

SHC

22.1

28.7

34.0

23.6

31.9

38.6

23.8

34.4

41.3

kW

4.57

4.55

4.50

4.59

4.56

4.52

4.58

4.57

4.54

125

TC

43.2

39.5

36.1

43.9

41.2

37.7

44.9

41.8

39.6

SHC

21.7

27.7

33.0

23.0

31.3

37.6

24.5

33.9

39.6

kW

5.10

5.05

5.02

5.11

5.08

5.05

5.13

5.09

5.08

549B060 (5 Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/Bf

1500/0.03

2000/0.05

2500/0.07

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

70.4

62.3

52.9

73.6

68.2

58.4

75.5

69.1

64.9

SHC

34.2

42.0

48.1

37.8

49.6

57.6

41.1

53.8

64.8

kW

3.75

3.73

3.58

3.80

3.80

3.69

3.83

3.74

3.75

85

TC

68.5

58.9

50.8

71.0

65.4

56.5

72.7

66.9

62.7

SHC

33.6

40.6

47.1

37.1

48.5

56.4

40.3

53.9

62.6

kW

4.20

4.16

4.03

4.24

4.23

4.12

4.27

4.20

4.17

95

TC

65.8

55.3

47.4

68.8

62.2

53.5

70.5

64.0

60.3

SHC

32.8

39.2

45.5

36.6

47.3

53.5

40.2

53.1

60.2

kW

4.69

4.63

4.49

4.75

4.70

4.60

4.78

4.68

4.67

105

TC

63.0

51.4

43.6

65.6

58.1

50.2

67.1

60.7

57.5

SHC

31.7

37.6

43.6

35.6

45.8

50.2

39.1

52.1

57.5

kW

5.22

5.13

5.00

5.27

5.21

5.12

5.30

5.22

5.20

115

TC

59.4

48.2

40.8

62.1

52.6

46.8

63.7

55.5

52.6

SHC

30.6

36.4

40.8

34.6

43.7

46.8

38.4

50.3

52.5

kW

5.83

5.70

5.59

5.87

5.77

5.70

5.89

5.81

5.77

125

TC

53.8

44.6

40.4

56.8

46.3

43.3

59.5

47.8

47.3

SHC

28.7

35.0

40.3

33.0

41.3

43.3

37.3

46.9

47.3

kW

6.44

6.30

6.21

6.50

6.36

6.32

6.54

6.40

6.39

Standard Ratings

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not

extrapolate.

2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator

coil

3. The SHC is based on 80 F edb temperature of air

entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from
SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

Bf

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity

(Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature
corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

total capacity

(Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR

DRY-BULB TEMP (F)

79

78

77

76

75

under

75

81

82

83

84

85

over

85

Correction Factor

.05

1.04 2.07 3.11 4.14 5.18

Use

formula

shown
below.

.10

.98 1.96 2.94 3.92 4.90

.20

.87 1.74 2.62 3.49 4.36

.30

.76 1.53 2.29 3.05 3.82

50T

F

Q

0

04
-0
12

549

B0
36-

12
0

This manual is related to the following products: