beautypg.com

Bryant 548F User Manual

Page 18

background image

18

MODEL NUMBER NOMENCLATURE — 548F UNITS

(ODS Model Number)

ARI* CAPACITY RATINGS

548F036-060

548F072-120

LEGEND

*Air Conditioning and Refrigeration Institute.

†Applies only to units with capacity of 60,000 Btuh or less.

**The IPLV applies only to 2-stage heat pump units.

††Not ASHRAE 90.1-99 compliant.

NOTES:
1. Rated in accordance with ARI Standards 210/240-95 and 270-95.
2. Ratings are net values, reflecting the effects of circulating fan heat.

3. Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db
air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db out-
door entering-air temperature.
High-Temp Heating Standard: 70 F db indoor entering-air temperature and 47 F
db, 43 F wb outdoor entering-air temperature.
Low-Temp Heating Standard: 70 F db indoor entering-air temperature and 17 F
db, 15 F wb outdoor entering-air temperature.

UNIT
548F

NOMINAL

TONS

COOLING

HEATING

(High Temp)

SOUND

RATING

(decibels)

Capacity

(Btuh)

SEER†

Capacity

(Btuh)

HSPF

Belt

Drive

Direct

Drive

036

3

35,600

10.20

10.00

34,400

6.7

84

048

4

46,500

10.00

9.70

46,500

7.0

80

060

5

57,000

10.00

9.90

57,000

7.5

82

UNIT
548F

NOMINAL

TONS

COOLING

HEATING

(High)

HEATING

(Low)

IPLV**

SOUND

RATING

(decibels)

Capacity

(Btuh)

EER

Capacity

(Btuh)

COP

Capacity

(Btuh)

COP

072††

6

70,000

9.05

72,400

3.20

42,000

2.14

82

090††

7

1

/

2

86,000

9.00

78,000

3.00

39,000

1.80

9.3

86

102††

8

1

/

2

96,000

8.90

96,000

3.00

55,000

2.00

8.85

86

120††

10

112,000

9.00

105,000

3.10

59,000

2.00

9.0

84

COP

Coefficient of Performance

db

dry bulb

EER

Energy Efficiency Ratio

HSPF

Heating Seasonal Performance Factor

IPLV

Integrated Part-Load Values

SEER

Seasonal Energy Efficiency Ratio

wb

wet bulb

Voltage Designation
E –
460-3-60
J – 208/230-1-60†
P – 208/230-3-60
T – 575-3-60

548F E X 090 000 AA

548F – Single-Package

Heat Pump
Unit

X – No Heat Installed.

(Field-installed electric heaters available.)

Factory-Installed Options*

Nominal Tons
036 –
3

090 – 7-1/2

048 – 4

102 – 8-1/2

060 – 5

120 – 10

072 – 6

Electric Heaters
000 –
No factory-installed electric heaters

LEGEND

*Refer to Trade Price Sheets or contact your local representative for specific

information regarding which options are available on which units.

†Single-phase is only available on 036-060 size units.

NOTE: The example model number 548FEX090000AA designates a 7

1

/

2

ton

460-3-60 volt electric heat pump unit with factory-installed economizer.

ODS

Order Distribution System

50

T

F

Q

0

04

-0

12

5

48F

036

-1

20

This manual is related to the following products: