CONTROLS (cont)

OPERATING MODES

BP — Building Pressurization:

Indoor fan on, economizer energized to fully open position, power exhaust disabled.

E

Evacuation:

Indoor fan off, economizer energized to fully open position, power exhaust on (open).

SD — Complete Unit Shutdown: Breaks 24-v power to the thermostat.
SP — Smoke Purge:

Indoor fan on, economizer energized to fully open position, power exhaust on.

See Legend on page 14.
*Included in power exhaust accessory.

LEGEND

Field Wiring

Field-Supplied Switch

Typical Smoke Control/Fire Shutdown Wiring — 542J150,180