beautypg.com

76 performance data (cont), Cooling capacities (cont) – Bryant 548F User Manual

Page 76

background image

76

PERFORMANCE DATA (cont)

COOLING CAPACITIES (cont)

549B072 (6 Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/Bf

1800/0.06

2100/0.066

2400/0.071

3000/0.088

Indoor Entering Air — Ewb (F)

72

67

62

57

72

67

62

57

72

67

62

57

72

67

62

57

75

TC

83.2 77.6 71.6 67.9 84.7 79.8 73.6 71.5 85.9 81.0 75.0 74.3 88.4 82.9 78.4 78.3

SHC

39.7 50.4 60.6 66.6 41.6 54.3 65.9 70.1 43.4 57.6 70.6 72.8 47.2 63.9 76.9 76.8

kW

4.90 4.78 4.69 4.63 4.94 4.84 4.71 4.69 4.97 4.86 4.74 4.73 5.04 4.91 4.81 4.81

85

TC

81.5 75.5 69.0 64.8 83.2 77.3 71.1 69.4 84.5 78.5 72.7 72.2 86.2 80.8 76.5 76.5

SHC

39.2 49.8 59.6 63.6 41.4 53.5 65.0 68.0 43.3 56.9 69.7 70.8 47.1 64.1 75.0 75.0

kW

5.45 5.34 5.23 5.16 5.49 5.36 5.27 5.23 5.52 5.38 5.29 5.27 5.57 5.45 5.36 5.36

95

TC

78.8 72.5 64.1 61.8 80.9 74.5 67.0 66.1 82.0 76.0 69.9 69.9 83.7 78.1 74.2 74.1

SHC

38.4 48.6 57.4 60.6 40.8 52.6 63.2 64.8 42.8 56.4 68.3 68.5 46.8 63.7 72.7 72.7

kW

6.03 5.91 5.79 5.73 6.09 5.96 5.84 5.82 6.11 6.00 5.89 5.89 6.16 6.05 5.96 5.96

105

TC

76.2 69.5 58.6 57.8 77.9 71.3 63.4 63.1 79.3 72.7 67.2 67.2 81.1 74.5 71.3 71.2

SHC

37.6 47.4 55.0 56.6 39.9 51.4 61.4 61.9 42.2 55.3 65.9 65.9 46.5 62.5 69.9 69.9

kW

6.69 6.56 6.40 6.38 6.73 6.61 6.45 6.44 6.77 6.64 6.51 6.51 6.82 6.67 6.57 6.57

115

TC

72.5 65.1 54.8 54.7 74.3 67.8 58.6 58.6 75.6 69.1 63.2 63.2 77.3 70.9 68.4 68.4

SHC

36.3 45.8 53.2 53.6 38.7 50.2 57.4 57.5 41.1 54.0 62.0 62.0 45.5 61.3 67.1 67.1

kW

7.37 7.24 7.08 7.07 7.43 7.30 7.16 7.16 7.48 7.34 7.21 7.21 7.52 7.38 7.32 7.32

549B090 (7

1

/

2

Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/Bf

2250/0.12

3000/0.15

3750/0.18

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

97.6

92.5

84.3

100.8

95.6

89.9

101.6

97.8

91.7

SHC

47.7

61.0

72.7

51.5

67.3

83.8

55.0

74.4

89.7

kW

5.80

5.76

5.73

5.86

5.78

5.78

5.86

5.82

5.73

85

TC

97.2

89.9

79.8

100.0

94.1

86.7

102.4

96.0

89.9

SHC

48.1

60.2

70.5

51.7

68.1

82.4

55.8

74.1

89.3

kW

6.61

6.50

6.43

6.65

6.56

6.62

6.69

6.58

6.50

95

TC

94.4

86.9

75.0

98.2

91.3

81.8

99.6

93.7

87.3

SHC

47.3

59.2

68.1

51.7

67.5

79.8

55.0

74.8

87.3

kW

7.43

7.37

7.19

7.50

7.41

7.30

7.50

7.43

7.35

105

TC

91.7

82.2

70.7

94.8

87.3

76.6

97.0

90.1

83.4

SHC

46.3

57.4

65.9

50.9

66.3

76.4

54.8

74.1

83.4

kW

8.37

8.22

8.04

8.39

8.33

8.15

8.44

8.35

8.26

115

TC

87.7

77.4

66.9

91.7

81.6

72.5

93.9

85.3

78.8

SHC

44.9

55.4

64.0

50.3

64.2

72.5

55.0

72.5

78.6

kW

9.33

9.16

8.98

9.44

9.27

9.11

9.48

9.33

9.22

125

TC

83.6

73.3

66.7

87.1

76.0

69.1

89.5

79.0

74.4

SHC

43.6

53.9

63.8

48.7

62.0

69.1

53.7

70.1

74.4

kW

10.38

10.16

9.94

10.49

10.27

10.14

10.53

10.36

10.25

549B120 (10 Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/Bf

3000/0.03

4000/0.04

5000/0.06

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

136.0

124.0

111.4

141.2

129.0

116.6

145.6

132.0

121.2

SHC

64.6

80.8

96.0

71.2

92.4

111.8

78.6

103.2

121.0

kW

7.51

7.35

7.20

7.61

7.45

7.29

7.72

7.53

7.39

85

TC

132.6

119.6

106.6

137.6

124.4

112.0

140.4

127.4

118.0

SHC

63.6

79.2

94.0

70.6

91.4

110.0

77.0

102.6

118.0

kW

8.40

8.23

8.09

8.50

8.33

8.17

8.58

8.40

8.27

95

TC

127.8

114.6

99.4

133.2

119.4

107.2

136.2

121.8

114.2

SHC

62.2

77.6

90.8

69.6

89.8

107.0

76.8

101.2

113.8

kW

9.36

9.18

9.01

9.48

9.30

9.15

9.56

9.36

9.24

105

TC

122.4

108.8

92.0

127.4

113.6

101.4

130.4

116.0

109.6

SHC

60.4

75.4

87.4

68.0

88.0

101.4

75.4

99.4

109.4

kW

10.41

10.26

10.02

10.53

10.35

10.22

10.63

10.43

10.35

115

TC

116.8

101.8

86.6

121.2

106.6

94.8

123.6

109.2

104.6

SHC

58.6

72.8

84.6

66.0

85.4

94.8

73.4

97.0

104.6

kW

11.58

11.37

11.15

11.68

11.51

11.35

11.76

11.60

11.51

125

TC

110.6

95.8

84.6

114.6

98.4

88.8

117.0

100.8

96.4

SHC

56.4

70.6

83.4

64.4

82.4

88.8

71.4

93.8

96.4

kW

12.87

12.62

12.36

12.97

12.73

12.60

13.03

12.83

12.77

Standard Ratings

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not

extrapolate.

2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evaporator

coil

3. The SHC is based on 80 F edb temperature of air

entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from
SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

Bf

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity

(Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature
corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

total capacity

(Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR

DRY-BULB TEMP (F)

79

78

77

76

75

under

75

81

82

83

84

85

over

85

Correction Factor

.05

1.04 2.07 3.11 4.14 5.18

Use

formula

shown
below.

.10

.98 1.96 2.94 3.92 4.90

.20

.87 1.74 2.62 3.49 4.36

.30

.76 1.53 2.29 3.05 3.82

50

T

F

Q

0

04

-0

12

5

49B

036

-120

This manual is related to the following products: