beautypg.com

Bryant 548F User Manual

Page 112

background image

112

PERFORMANCE DATA (cont)

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 542J150,180

LEGEND

*Units with electric heat are not designed to operate at these ranges.

NOTES:

1. Heaters are rated at 208/240 v and 480 v.
2. The static pressure must be added to external static pressure. The

sum and the indoor-air section entering-air cfm should then be
used in conjunction with the Fan Performance table to determine
blower rpm, bhp, and watts.

FAN RPM AT MOTOR PULLEY SETTINGS* — 542J150,180

*Approximate fan rpm shown.

†Standard motor with standard drive.

**Standard motor with alternate drive.

ACCESSORY/FIOP

UNIT SIZE

UNIT VOLTAGE

kW

CFM

3750

4500

5000

5600

6000

6250

7200

7500

Electric Heaters

150

208/230-3-60

14-34

0.05

0.05

0.07

0.08

0.09

0.09

0.11

0.12

42,56

0.06

0.06

0.08

0.10

0.12

0.13

0.16

0.17

460-3-60

15,32

0.05

0.05

0.07

0.08

0.09

0.09

0.11

0.12

55

0.06

0.06

0.08

0.10

0.12

0.13

0.15

0.15

180

208/230-3-60

26,34

*

*

*

0.08

0.09

0.09

0.11

0.12

42,56

0.10

0.12

0.13

0.16

0.17

460-3-60

32,55

*

*

*

0.08

0.09

0.09

0.11

0.12

0.10

0.12

0.13

0.15

0.17

EconoMi$er

All

All

0.03

0.03

0.05

0.06

0.07

0.07

0.09

0.10

Glycol Coil

All

All

0.16

0.18

0.25

0.31

0.35

0.37

0.44

0.46

FIOP — Factory-Installed Option

UNIT

542J

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

150†

1179

1150

1121

1093

1064

1035

1006

978

949

920

891

150**

1559

1522

1488

1455

1422

1389

1356

1323

1289

1256

1227

180†

1038

1023

1001

979

956

934

912

890

868

846

817

180**

1303

1288

1266

1244

1222

1199

1177

1155

1133

1111

1082

Fan Performance Using Accessory Power Exhaust

5

0

T

F

Q0

04-

01

2

54

2J1

50,

1

8

0

This manual is related to the following products: