Bryant 548F User Manual
Page 78
78
PERFORMANCE DATA (cont)
INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont)
LEGEND
NOTES:
1.
indicates integrated ratings.
2. Integrated capacity is maximum (instantaneous) capacity less the
effect of frost on the outdoor coil and the heat required to defrost it.
549B060 (5 Tons)
Return
Air
(F db)
Cfm
(Standard
Air)
Temperature Air Entering Outdoor Coil (F db at 70% rh)
–20
–10
0
10
17
30
40
47
50
60
55
1500
Cap. 19.4 17.8 24.8 22.8 29.7 27.3 34.7 31.8 38.5 35.1 46.8 41.0 53.9 53.9 59.5 59.5 62.1 62.1 71.9 71.9
kW
3.28
3.53
3.67
3.77
3.85
4.04
4.21
4.36
4.43
4.73
2000
Cap. 20.7 19.0 25.9 23.8 30.6 28.1 35.6 32.6 39.5 36.0 48.0 42.1 55.4 55.4 61.1 61.1 63.8 63.8 73.3 73.3
kW
3.48
3.68
3.77
3.84
3.90
4.04
4.18
4.30
4.37
4.60
2500
Cap. 21.7 20.0 26.8 24.7 31.4 28.9 36.4 33.4 40.4 36.8 49.0 42.9 56.5 56.5 62.2 62.2 65.0 65.0 72.1 72.1
kW
3.69
3.85
3.92
3.98
4.03
4.15
4.28
4.40
4.46
4.61
70
1500
Cap. 14.5 13.3 21.8 20.0 28.2 26.0 34.0 31.2 37.8 34.5 45.7 40.1 52.4 52.4 57.7 57.7 60.2 60.2 69.5 69.5
kW
3.20
3.71
4.07
4.30
4.42
4.64
4.83
5.00
5.08
5.40
2000
Cap. 15.9 14.7 23.3 21.4 29.5 27.1 34.9 32.1 38.7 35.3 46.8 41.0 53.7 53.7 59.3 59.3 61.8 61.8 71.5 71.5
kW
3.44
3.91
4.20
4.36
4.43
4.59
4.74
4.87
4.94
5.21
2500
Cap. 17.2 15.8 24.5 22.5 30.5 28.1 35.8 32.9 39.6 36.1 47.8 41.9 54.8 54.8 60.4 60.4 63.1 63.1 72.4 72.4
kW
3.67
4.11
4.35
4.47
4.53
4.66
4.79
4.91
4.97
5.21
80
1500
Cap.
9.9
9.1
18.3 16.8 25.9 23.8 32.8 30.1 37.0 33.8 45.1 39.5 51.6 51.6 56.7 56.7 59.1 59.1 68.1 68.1
kW
3.04
3.66
4.20
4.60
4.80
5.10
5.32
5.49
5.58
5.92
2000
Cap. 11.2 10.3 20.0 18.4 27.5 25.3 34.2 31.4 38.2 34.8 46.1 40.4 52.8 52.8 58.1 58.1 60.6 60.6 70.0 70.0
kW
3.27
3.89
4.38
4.69
4.83
5.02
5.18
5.32
5.38
5.66
2500
Cap. 12.4 11.4 21.3 19.6 28.8 26.5 35.1 32.3 39.1 35.6 47.1 41.2 53.9 53.9 59.3 59.3 61.8 61.8 71.4 71.4
kW
3.50
4.12
4.56
4.81
4.92
5.07
5.20
5.32
5.38
5.65
549B072 (6 Tons)
Return
Air
(F db)
Cfm
(Standard
Air)
Temperature Air Entering Outdoor Coil (F db at 70% rh)
–20
–10
0
10
17
30
40
47
50
60
55
1800
Cap. 16.5 15.2 20.8 19.1 26.4 22.4 33.6 30.8 41.0 37.6 51.3 44.9 61.9 61.9 69.5 69.5 78.0 78.0 77.9 77.9
kW
3.50
3.63
3.79
4.01
4.18
4.57
4.94
5.22
5.57
5.55
2100
Cap. 16.9 15.5 21.2 19.5 27.2 23.1 34.9 32.0 41.8 38.3 52.2 45.8 63.2 63.2 69.6 69.6 75.7 75.7 76.5 76.5
kW
3.56
3.68
3.84
4.04
4.18
4.54
4.86
5.07
5.30
5.32
2400
Cap. 17.2 15.9 21.8 20.0 28.0 23.8 35.6 32.6 43.1 39.5 53.8 47.2 64.1 64.1 69.0 69.0 74.8 74.8 74.3 74.3
kW
3.64
3.75
3.89
4.08
4.21
4.54
4.82
4.97
5.18
5.15
3000
Cap.
18
16.5 23.0 21.1 29.4 25.0 37.4 34.4 45.2 41.4 56.6 49.6 63.2 63.2 65.5 65.5 69.8 69.8 70.6 70.6
kW
3.79
3.90
4.03
4.19
4.32
4.61
4.77
4.84
4.98
4.99
70
1800
Cap. 15.2 14.0 18.2 16.7 24.1 20.5 31.1 28.5 38.0 34.8 47.7 41.8 58.4 58.4 67.1 67.1 78.0 78.0 77.9 77.9
kW
3.97
4.12
4.33
4.57
4.75
5.19
5.59
5.94
6.43
6.41
2100
Cap. 15.6 14.4 18.6 17.1 24.8 21.1 32.0 29.4 39.1 35.9 49.1 43.1 59.7 59.7 68.5 68.5 77.3 77.3 76.7 76.7
kW
4.04
4.18
4.37
4.59
4.76
5.15
5.51
5.81
6.17
6.13
2400
Cap. 16.1 14.8 19.0 17.5 25.9 22.0 32.7 30.0 39.9 36.6 51.1 44.7 61.3 61.3 69.0 69.0 75.6 75.6 76.3 76.3
kW
4.11
4.24
4.43
4.63
4.79
5.17
5.48
5.73
5.97
5.99
3000
Cap. 16.8 15.5 19.7 18.1 26.7 22.7 34.3 31.5 41.8 38.3 53.5 46.8 63.7 63.7 68.3 68.3 73.0 73.0 73.8 73.8
kW
4.28
4.39
4.56
4.75
4.89
5.22
5.49
5.63
5.80
5.82
80
1800
Cap. 13.6 12.5 17.1 15.7 21.7 18.4 29.2 26.8 36.5 33.4 45.6 40.0 55.3 55.3 64.2 64.2 77.2 77.2 76.9 76.9
kW
4.20
4.46
4.67
4.95
5.16
5.62
6.02
6.40
7.00
6.98
2100
Cap. 14.1 13.0 17.6 16.2 22.6 19.2 30.1 27.6 37.1 34.0 46.9 41.1 57.0 57.0 66.4 66.4 76.3 76.3 77.2 77.2
kW
4.28
4.52
4.72
4.98
5.16
5.58
5.95
6.30
6.71
6.74
2400
Cap. 14.5 13.4 18.0 16.6 23.1 19.6 31.2 28.7 37.9 32.7 48.5 42.5 58.7 58.7 67.7 67.7 76.3 76.3 75.9 75.9
kW
4.37
4.59
4.77
5.03
34.7
5.59
5.93
6.23
6.57
6.54
3000
Cap. 15.4 14.1 18.8 17.3 24.1 20.5 32.2 29.6 39.6 36.3 50.4 44.2 61.6 61.6 68.9 68.9 74.3 74.3 74.5 74.5
kW
4.54
4.74
4.91
5.14
5.29
5.64
5.95
6.17
6.37
6.36
Cap. — Heating Capacity (1000 Btuh) (includes indoor-fan motor heat)
kW
— Total Power Input (includes compressor motor power input,
outdoor-fan motor input, and indoor-fan motor input)
rh
— Relative Humidity
50
T
F
Q
0
04
-0
12
5
49B
036
-120