Close the case and fix in place with the plastic screws.

Switch on the controller.

Push and HOLD the DISP button until the parameter menu appears (Par). Push the

SEL

button repeatedly until the “br” (=bit rate) sign appears: this is the first parameter

of the communication module. Set the desired bit rate using the +/- buttons.
Throughout the communication system all devices must use the same bit rate !

Push

the

SEL

button - the “bPAr.n” sign will appear. Using the +/- buttons set the type

of bit parity: n:none, o:odd, E:even.

Push

the

SEL

button and using +/- select the format: “bASCII” equals ASCII (7bit)

format; or “b rtu” equals RTU (8bit) format.

Push

the

SEL

button - the network address of the controller will appear:

bA 02”. Set the desired unique address with the +/- buttons.

When finished, push the DISP (display) button to go back to the base display mode.

Switch off the controller: BOTH the I/O switch and the external main electrical switch.

Open the case again and slide the “Setup” switch to the “Off” position (in the outer part

of the case, to the left of the battery).

Close the case, tighten the four large fastening screws, switch “On” the external main

electrical switch, and switch “On” the controller.

The Module installation is completed.