Schwank ThermoControl Plus Series CM-485 User Manual
Page 5

- 5 -
Close the case and fix in place with the plastic screws.
Switch on the controller.
Push and HOLD the DISP button until the parameter menu appears (Par). Push the
SEL
button repeatedly until the “br” (=bit rate) sign appears: this is the first parameter
of the communication module. Set the desired bit rate using the +/- buttons.
Throughout the communication system all devices must use the same bit rate !
Push
the
SEL
button - the “bPAr.n” sign will appear. Using the +/- buttons set the type
of bit parity: n:none, o:odd, E:even.
Push
the
SEL
button and using +/- select the format: “bASCII” equals ASCII (7bit)
format; or “b rtu” equals RTU (8bit) format.
Push
the
SEL
button - the network address of the controller will appear:
”bA 02”. Set the desired unique address with the +/- buttons.
When finished, push the DISP (display) button to go back to the base display mode.
Switch off the controller: BOTH the I/O switch and the external main electrical switch.
Open the case again and slide the “Setup” switch to the “Off” position (in the outer part
of the case, to the left of the battery).
Close the case, tighten the four large fastening screws, switch “On” the external main
electrical switch, and switch “On” the controller.
The Module installation is completed.