*008Eh: The measured and displayed room temperature ×10 with sign in Zone4
*0090h: The measured and displayed room temperature ×10 with sign in Zone5
*0092h: The measured and displayed room temperature ×10 with sign in Zone6
*0094h: The measured and displayed room temperature ×10 with sign in Zone7
*0096h: The measured and displayed room temperature ×10 with sign in Zone8
*0098h: State of the heater relays in Zone1: 1 if the relay is switched On
In case of P0, P1 application programs:
bit7
: State of Relay 1
In case of P2, P3, P4, P5 application programs:
bit7
: State of Relay 1
bit6
: State of Relay 2
*009Ah: State of the heater relays in Zone2:
In case of P0, P1 application programs:
bit6
: State of Relay 2
In case of P2 application programs:
bit5
: State of Relay 3
In case of P3, P4, P5 application programs:
bit5
: State of Relay 3
bit4
: In case of P2 application programs:
*009Ch: State of the heater relays in Zone3:
In case of P0, P1 application programs:
bit5
: State of Relay 3
In case of P2 application programs:
bit4
: State of Relay 4
In case of P3 application programs:
bit3
: State of Relay 5
In case of P4, P5 application programs:
bit3
: State of Relay 5
bit2
: State of Relay 6
*009Eh: State of the heater relays in Zone4:
In case of P0, P1 application programs:
bit4
: State of Relay 4
In case of P2 application programs:
bit3
: State of Relay 5
In case of P3 application programs:
bit2
: State of Relay 6
In case of P4 application programs:
bit1
: State of Relay 7
In case of P5 application programs:
bit1
: State of Relay 7
bit0
: State of Relay 8
*00A0h: State of the heater relays in Zone5:
In case of P0, P1 application programs:
bit3
: State of Relay 5
In case of P2 application programs:
bit2
: State of Relay 6
In case of P3 application programs:
bit1
: State of Relay 7
In case of P4 application programs:
bit0
: State of Relay 8
*00A2h: State of the heater relays in Zone6: