Error Caused
by
83h Month>12
84h
Too many days
85h Year<8,
Year>50
89h
A manual setting
is presently going
on at the unit
8Ah
Ending date is
earlier than
starting date
Reading out the holiday program
Load 0022h into register 0144h.
:02060144002292
As a result the data of the eight holiday programs will be loaded to register area 0144h-
0173h.
To read out the data of holiday program 1 from address 0144h :020301440003B4
In the answer we will get all data of holiday program 1:
:020306121203030808BB
Read out address 0174h :02030174000181
It will show which ones of the 8 programs are presently switched on (On/Off Mask):
:020302A00059
HOL.
1 2 3 4 5 6 7 8
80h 40h 20h 10h 8h 4h 2h 1h
On
x x
Writing the holiday program
Load the table (0144h – 0173h) with the necessary data in the following order: start day,
end day, start month, end month, start year, end year. Year must be given as 08 not
2008.
After this write into address 0174h the "On/Off Mask" (see above) and 41h.
Command 41h will start the writing procedure. :02060174A041A3
Then read out area 0174h – 0175h.
:02030174000186
In the answer we will get the On/Off Mask and the
possible errors.
:020302A00059
Error information
On/Off
Mask
If the value of the error is 0 the writing is carried
out.
Possible Error types and codes are listed here.
In
case of any error the writing of the good data will
also be prohibited. Data checking will be carried
out
only at the on-state programs.
Content Value
Start day
18
End day
18
Start month
03
End month
03
Start year
2008
End year
2008