Schwank ThermoControl Plus Series CM-485 User Manual
Page 10

- 10 -
0046h: No
function
0048h: No
function
004Ah: No
function
004Ch: Zone1 Frost protection value ×10 with sign. This value acts as a low limit for all
of the other set values. Factory settings: 0050h 8.0°C
004Eh: Zone2 Frost protection value ×10 with sign.
0050h: No
function
0052h: No
function
0054h: No
function
0056h: No
function
0058h: No
function
005Ah: No
function
*005Ch: Selected application program (P0, P1, P2) number. At this type: 0, 1, 2
*005Eh: Number of Zones as configured. Max: 2 at this type.
*0060h: Error signals: in case of an error the corresponding bit: 1
bit7
: Error relay is on (relay contacts closed)
bit6
: Sensor Error
bit2
: Button is stuck
bit1
: Alarm signal (contact input is opened)
bit0
: Battery is low (discharged)
*0062h: State of the contact inputs (a closed contact sets the bit to 1):
bit2
: “Error” (Störung) contact
bit1
: “Alarm” contact
bit0
: “Remote” contact
*0064h: Outside temperature ×10 with sign. Example: FFE2h –3.0°C
When ATF sensor is not connected: F830h (-200.0)
*0066h: bit0: State of the ventilator relay: 1 if relay is on (relay contacts closed)
*0068h: State of Zone 1:
bit7
: 1 when Zone 1 is enabled (see: 000Ch)
bit6
: 1 when there is a sensor error in Zone 1
bit5
: 1 when “Error” (Störung) contact is closed
bit3
: 1 when Ventilator relay is on,
bit2
: 1 when heater is operated with full load (Stage 2) in Zone 1
bit1
: 1 when heater is operated with part load (Stage 1) in Zone 1
bit0
: 1 when selected control mode is 2-stage in Zone 1;
0 when selected control mode is 1-stage in Zone 1
*006Ah: State of Zone 2: format same as at Zone 1.
*006Ch: No function
*006Eh: No function
*0070h: No function
*0072h: No function
*0074h: No function
*0076h: No function
*0078h: Zone1 Actual set value ×10 with sign, the controller presently tries to keep this
temperature value.
*007Ah: Zone2 Actual set value ×10 with sign.
*007Ch: No function
*007Eh: No function
*0080h: No function
*0082h: No function
*0084h: No function