*0092h: No function
*0094h: No function
*0096h: No function
*0098h: State of the heater relays in Zone1: 1 if the relay is switched On
In case of P0, P1 application programs:
bit7
: State of Relay 1
In case of P2, P3 application programs:
bit7
: State of Relay 1
bit6
: State of Relay 2
*009Ah: State of the heater relays in Zone2:
In case of P0, P1 application programs:
bit6
: State of Relay 2
In case of P2 application program:
bit5
: State of Relay 3
In case of P3 application program:
bit5
: State of Relay 3
bit4
: State of Relay 4
*009Ch: State of the heater relays in Zone3:
In case of P0, P1 application programs:
bit5
: State of Relay 3
In case of P2 application program:
bit4
: State of Relay 4
*009Eh: State of the heater relays in Zone4:
In case of P0, P1 application programs:
bit4
: State of Relay 4
*00A0h: No function
*00A2h: No function
*00A4h: No function
*00A6h: No function
*00A8h: 0 if the maintenance warning counter is switched off (not operating)
*00AAh: Remaining working hours till the next maintenance time
*00ACh: Selected length of the maintenance period (the number of hours)
*00C6h: Work-hour counter content for Relay 1; 4byte length
*00CAh: Work-hour counter content for Relay 2; 4byte length
*00CEh: Work-hour counter content for Relay 3; 4byte length
*00D2h: Work-hour counter content for Relay 4; 4byte length
*00D6h: No function
*00DAh: No function
*00DEh: No function
*00E2h: No function
*01C0h: Serial number of the controller, length: 6 ASCII characters
*01C6h: Name of the controller, max. 10 characters, the end is indicated with “0” (TC
Plus 2)