beautypg.com

Schwank ThermoControl Plus Series CM-485 User Manual

Page 21

background image

- 21 -

Error Caused

by

82h Minute>1439
84h

Group of days=0

86h

Inactive program is

followed by an active one

87h

Two different programs

at the same time

88h

The given zone number

is not existing in the unit

89h

A manual setting is

presently going on at the

unit

Writing time program into a Zone

The switching parameters must be loaded into 00F6h-0141h.
After this the Zone Nr. and 41h must be loaded into address 0142h
Command 41h will start the writing procedure.

:02060142014174

To check result read out 0142h-0143h:

:020301420001B8

The answer will indicate Zone Nr. and Error state
:0203020100F8

Error information


Writing is completed if Error is 0.
Possible Error types and codes are listed here:
In case of any error the writing of the good data will
also be prohibited. Data checking will be carried out
only at active-state programs.
The same program can be writing into different
zones. To do this write new data only into 0142h-
0143h registers.







Holiday program registers overview


The table below contains the register addresses of the different holiday programs..
All the data of a holiday program is stored in three 16-bit registers.

Program Nr Address

Program Nr. Address

1 0144h

5 015Ch

2 014Ah

6 0162h

3 0150h

7 0168h

4 0156h

8 016Eh

0174h 0175h

On / Off

Command / Error

On / Off:

The switched-on program is indicated by a bit 1

Commands:

22h: Load the eight holiday programs into the registers.

41h: Write content of the registers into the eight holiday programs.

Error:

See at chapter “Writing the holiday program”