Error Caused
by
82h Minute>1439
84h
Group of days=0
86h
Inactive program is
followed by an active one
87h
Two different programs
at the same time
88h
The given zone number
is not existing in the unit
89h
A manual setting is
presently going on at the
unit
Writing time program into a Zone
The switching parameters must be loaded into 00F6h-0141h.
After this the Zone Nr. and 41h must be loaded into address 0142h
Command 41h will start the writing procedure.
:02060142014174
To check result read out 0142h-0143h:
:020301420001B8
The answer will indicate Zone Nr. and Error state
:0203020100F8
Error information
Writing is completed if Error is 0.
Possible Error types and codes are listed here:
In case of any error the writing of the good data will
also be prohibited. Data checking will be carried out
only at active-state programs.
The same program can be writing into different
zones. To do this write new data only into 0142h-
0143h registers.
Holiday program registers overview
The table below contains the register addresses of the different holiday programs..
All the data of a holiday program is stored in three 16-bit registers.
Program Nr Address
Program Nr. Address
1 0144h
5 015Ch
2 014Ah
6 0162h
3 0150h
7 0168h
4 0156h
8 016Eh
0174h 0175h
On / Off
Command / Error
On / Off:
The switched-on program is indicated by a bit 1
Commands:
22h: Load the eight holiday programs into the registers.
41h: Write content of the registers into the eight holiday programs.
Error: