2 receive, Receive, Appendix – Lenze EMF2102IB User Manual
Page 53

Appendix
8-21
L
_^ONMObk
8.3.2
RECEIVE
The command RECEIVE is to request parameter values of the Lenze controllers. The code numbers
of the requested parameter are transmitted via the RECEIVE telegram using the following structure:
EOT
AD1
AD2
C1
C2
ENQ
The abbreviations have the following meanings:
EOT (04
hex
)
End of the (previous) transmission
AD1, AD2
Logic unit address of the slave to be addressed
C1, C2
Code number (two ASCII characters)
or extended addressing
ENQ (05
hex
)
Station request
Structure and meaning of the code numbers (C1, C2) and the controller address (AD1, AD2) are
described in the corresponding paragraphs of the chapter SEND (see page 8-23).
Telegram response
The Lenze controller addressed via a RECEIVE telegram generates one of the following responses:
•
The controller could decode the request and is now sending the requested parameter value
to the host.
STX
C1
C2
V1
...
Vn
ETX
BCC
•
The controller could decode the request, however, a check-sum fault (parity fault) occurred
during transmission.
STX
C1
C2
?
ETX
BCC
•
The controller could not process the request because the requested code number does not
exist.
STX
C1
C2
EOT
The abbreviations have the following meanings:
STX (02
hex
)
Start of text
C1, C2
Code number (two ASCII characters)
or extended addressing
V1 to Vn
Parameter value (n ASCII characters)
ETX (03
hex
)
End of text
BCC
Block-check character (00
¼ FF
hex
)
? (3F
hex
)
ASCII character ” ?”
EOT (04
hex
)
End of the (previous) transmission
Structure and meaning of the block-check character (BCC) are described in the corresponding
paragraph of the chapter SEND (see page 8-20).