3 creating a project folder, 4 storing the device data base files (gse), Creating a project folder – Lenze PROFIBU PC-based Automation User Manual
Page 24: Storing the device data base files (gse), Storing the device data base files (gse) ( 24)

Control technology | PROFIBUS communication manual
Commissioning of PROFIBUS
Detailed commissioning steps
24
L
DMS 2.2 EN 07/2011 TD17
6.2.3
Creating a project folder
Create a project folder on the engineering PC.
Use this project folder to store the below data generated in the different project
configuration steps:
Project data created in the »Engineer« or »GDC«
The project file created in the »PLC Designer«
Project data of other engineering tools
Tip!
Create a separate project folder for every PROFIBUS configuration for storing the
project files.
6.2.4
Storing the device data base files (GSE)
The data of the bus pheripherals required for the master control are stored in a GSE file.
This file is required for programming the control.
Current GSE files (e.g. for the I/O system IP20 or for Lenze PROFIBUS communication
modules) can be downloaded in the Download area at
http://www.Lenze.com
.
Store the required GSE files in the »PLC Designer« target directory:
C:\...\Lenze\PlcDesigner\Targets\L-force_Logic_x800_V8\PlcConfPCMatic
C:\...\Lenze\PlcDesigner\Targets\L-force_Motion_x800_V8\PlcConfPCMaticMotion
Tip!
The GSE files can also be stored via the »PLC Designer« with the menu command
ExtrasAdd configuration file.
Note!
PROFIBUS can be used in motion and logic systems. In the Lenze control system,
PROFIBUS is the logic bus. Only use PROFIBUS in a motion system if an additional
motion bus (e.g. CAN) is used.