Technical data, General data and operating conditions – Lenze 8400 motec Manual User Manual
Page 27
Technical data
General data and operating conditions
l
27
EDS84DG752 EN 4.0
Protection of persons and equipment
Enclosure
EN 60529
IP65
optional: IP66
in ready−for−use state:
l
Close unused bores for cable
glands with blanking plugs!
l
Close unused connectors with
protection covers or blanking
plugs!
NEMA 250
Protection according to
l
Type 4
(Earth) leakage current
EN 61800−5−1
> 3.5 mA AC, > 10 mA DC
Observe the regulations and
safety instructions!
Total fault current
In TN systems the following earth−leakage circuit breakers
can be used:
Motor mounting
E84DGDVB3714
...
E84DGDVB1524
30 mA, type B
E84DGDVB2224
...
E84DGDVB7524
300 mA, type B
Wall mounting
E84DGDVB3714
...
E84DGDVB7524
300 mA, type B
Additional equipotential
bonding
M5 thread with terminal in the WU for connection of a
16mm
@ PE cable
Protective insulation of
control circuits
EN 61800−5−1
Safe isolation from mains by double (reinforced) insulation
Insulation resistance
EN 61800−5−1
Site altitude
0 ... 2000 m Overvoltage category III
2000 ... 4000 m Overvoltage category II
Short−circuit strength
EN 61800−5−1
Connection:
Motor
To a limited extent, the
controller is inhibited, error
acknowledgement required
Motor holding brake, brake
resistor
No
PTC, control terminals
Full
Earth−fault strength
EN 61800−5−1
Connection:
Motor (at controller
enable)
To a limited extent, the
controller is inhibited, error
acknowledgement required
Motor (during operation)
No
Brake resistor, PTC
No
Protective measures
against
l
Short circuit on the motor side at switch−on and during
operation
l
Motor stalling
l
Motor overtemperature
– Input for PTC or thermal contact
– I
2
t monitoring
Cyclic mains switching
l
Switchings/minute
3
l
Switchings/hour
Max. 20
l
Switching pause
After switching the mains 3
times in one minute, there must
be a switching pause of
9 minutes.
Starting current
£ 2 x I
N