JUMO dTRANS T05
Programmable 2-Wire Transmitter
- For installation into terminal head form B
- For installation on DIN rail
Brief description
The transmitters detect sensor signals by means of RTD temperature probes, thermocouples,
resistance transmitters, or resistors/potentiometers. When using a resistor/potentiometer or RTD
temperature probe, the sensor connection on the input side can be connected with a 2-wire, 3-
wire, or 4-wire circuit. Voltage signals in the range from -100 to +1100 mV can also be detected.
Depending on the selected measuring input the linearization variants linear, temperature-linear,
and the possibility of an easy configurable as well as customer-specific linearization are avail-
able.
Type 707050 delivers 4 to 20 mA as an output signal. Type 707051 offers an output signal of 4
to 20 mA or 0 to 10 V. The measuring input and the output signal are electrically isolated from
each other. Reversion of the output signal is possible for both types.
The transmitter configuration with respect to probe type, connection technology of the probe,
measuring range (freely adjustable), and linearization is carried out by means of a setup program
on the PC. The connection to the PC is established via a USB interface which does not require
additional auxiliary voltage. Via the USB interface the min./max. process value and the min./max.
operating temperature detected by the transmitter can be read and the sensor wiring can be
checked online.
The operating status of the transmitter is indicated by a two-color control LED (red/green). This
is lit green during operation without malfunctions. If a malfunction such as a probe break occurs
then the signal starts flashing.
Type 707050 (dTRANS T05 B)
Type 707051 (dTRANS T05 T)
Block diagram
T
ransmitter
707050
707051
: 4 to 20 mA
: 4 to 20 mA
0 to 10 V
Output signals:
Supply voltage:
Setup
USB-interface:
Voltage
+
-
RTD
temperature probe
Resistance
transmitter
Input signals:
Thermocouple
DC 11 to 35 V
Resistor/
potentiometer
Special features
• Measuring input for RTD temperature
probe, thermocouple, resistor/potentiome-
ter,
resistance transmitter, and voltage
• Input and output are electrically isolated
• Control LED (red/green)
• Configuration directly via USB cable
(Mini-B) without additional auxiliary voltage
• Customer-specific linearization
• Detection of the min./max. process value
(drag pointer function including point in
time)
• Option to specify the temperature in °F for
temperature sensors
• Type 707051 available with screw terminals
or spring-cage terminals