JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Data Sheet User Manual

Page 3

background image

2012-07-01/00540116

Data Sheet 701150

Page 3/14

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
8 Technology Boulevard
Canastota, NY 13032, USA
Phone: 315-697-5866

1-800-554-JUMO

Fax:

315-697-5867

E-mail:

[email protected]

Internet: www.jumousa.com

Binary input

Relay outputs

Measuring circuit monitoring

Voltage supply

Test voltages according to EN 60730, part 1

Electrical safety

Connection

Function

1 floating contact

Unlocking, key inhibit, level inhibit can be configured

Relay output KV

Relay (changeover contact) without contact protection

30000 switching operations at a switching capacity of 250 V, 3 A, 50 Hz (resistive load)

or up to DC 30 V, 3 A. Minimum current DC 12 V, 100 mA.

Relay output alarm

Relay (changeover contact)
Contact protection circuit:

fuse cut-out 3.15 AT, installed in the N/O contact arm

30000 switching actions at a switching capacity of 230 V, 3 A, 50 Hz (resistive load)

or up to DC 30 V, 3 A. Minimum current DC 12 V, 100 mA.

RTD temperature probe in 3-wire
circuit and double thermocouples

Thermocouples

Current 4 to 20 mA

Overrange
and underrange

Is detected
LED K1, K2, KD, and KV are lit;
">>>>“ flashes in the display for overrange, "<<<<“ for underrange.

Probe/cable break

Is detected
LED K1, K2, KD, and KV are lit
">>>>“ flashes in the display; relay output alarm is inactive

LED K1, K2, KD, and KV are lit;
">>>>“ flashes in the display;
relay output alarm is inactive

Probe short circuit

Is detected
LED K1, K2, KD, and KV are lit
"<<<<“ flashes in the display;
relay output alarm is inactive

Is detected by difference monitor-
ing of the analog inputs

LED K1, K2, KD, and KV are lit;
"<<<<“ flashes in the display;
relay output alarm is inactive

Voltage supply

AC/DC 20 to 30V, 48 to 63 Hz,
AC 110 to 240V +10% /-15%, 48 to 63 Hz

Power consumption

12 VA

Power loss

< 12 W

Input and output against voltage supply
- At voltage supply AC 110 to 240 V +10 % / -15 %

3.7 kV/50 Hz

- At voltage supply AC/DC 20 to 30 V, 48 to 63 Hz

3.7 kV/50 Hz

Clearances / creepage distances

Mains voltage to electronic compo-
nents and probes

6 mm

/

8 mm

Mains voltage to the relay

6 mm

/

8 mm

Relay to electronic components and
probes

6 mm

/

8 mm

Electrical safety

According to DIN EN 14597 (DIN EN 60730-2-9)
Overvoltage category III, pollution degree 2

Protection rating I

With internal separation to SELV electrical circuits