Safety temperature limiter stb – JUMO 701150 14597 safetyM STB/STW - Safety Temperature Limiter and Safety Temperature Monitor Data Sheet User Manual
Page 10

Page 10/14
Data Sheet 701150
2012-07-01/00540116
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone:
+49 661 6003-0
Fax:
+49 661 6003-607
E-mail:
Internet:
www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:
+44 1279 635262
E-mail:
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
8 Technology Boulevard
Canastota, NY 13032, USA
Phone: 315-697-5866
1-800-554-JUMO
Fax:
315-697-5867
E-mail:
Internet: www.jumousa.com
Probes for water and oil
Probes for water, oil, and air
Safety control and regulating devices
Safety temperature monitor STW
1
The safety temperature monitor is a device that is automatically reset when activated once the sensor temperature has fallen below or risen
above the set limit value by an amount equal to the switching differential. Possible settings: monitoring for limit value overrange or underrange.
Mode of operations:
Minimum requirements: 2B, 2K, 2P
Additional requirements: 2N, 2D
Safety temperature limiter STB
1
The safety temperature limiter is a device that is permanently locked after responding.
Manual reset using the RESET key is possible once the probe temperature has fallen below / has exceeded the limit value by the amount of the
switching differential. Possible settings: monitoring for overrange or underrange.
Mode of operations:
Minimum requirements: 2B, 2J, 2V, 2K, 2P and adjustable with special tools
Additional requirements: 2N, 2F, 2D
1.
For more detailed explanation, see DIN EN 14 597.
Note:
The probes described in data sheets 901006 and 902006 are also certified for the Pressure Equipment Directive
Note: Because of the high response accuracy, only use thermowells (pockets) that are included in the scope of delivery.
Actual type designation
Old type
designation
Probe type
Temperature range
Nom. length mm
P
rocess connection
RTD temperature probe Data Sheet 90.2006
902006/53-505-2003-1-12-190-815/000
90D239-F03
2 x Pt100
-40 ... +400 °C
190
902006/53-507-2003-1-12-100-815/000
90.239-F02
2 x Pt100
(arranged one
below the other
in protection tube)
-40 ... +480 °C
100
902006/53-507-2003-1-12-160-815/000
90.239-F12
160
902006/53-507-2003-1-12-190-815/000
190
902006/53-507-2003-1-12-220-815/000
90.239-F22
220
902006/53-507-1003-1-12-100-815/000
90.239-F01
1 x Pt100
-40 ... +480 °C
100
weld-in sleeve
902006/53-507-1003-1-12-160-815/000
90.239-F11
160
902006/53-507-1003-1-12-220-815/000
90.239-F21
220
902006/53-505-1003-1-12-190-815/000
90.239-F03
1 x Pt100
-40 ... +400 °C
190
902006/53-505-3003-1-12-100-815/000
90.239-F07
3 x Pt100
-40 ... +400 °C
100
902006/53-505-3003-1-12-160-815/000
90.239-F17
160
902006/53-505-3003-1-12-220-815/000
90.239-F27
220
902006/40-226-1003-1-12-220-815/000
90.280-F30
1 x Pt100
-170 ... +480°C
220
weld-in sleeve
902006/40-226-1003-1-12-160-815/000
90.280-F31
160
902006/40-226-1003-1-12-100-815/000
90.280-F32
100
Thermocouples Data Sheet 90.1006
901006/53-543-1042-12-220-815/000
90.111-F01
1 x Fe-CuNi Type „L“
-35 ... 480°C
220
weld-in sleeve
901006/53-543-2042-12-220-815/000
90.111-F02
2 x Fe-CuNi Type „L“
220
Note: Because of the high response accuracy, the use of thermowells (pockets) is not admissible.
Actual type designation
Old type
designation
Probe type
Temperature range
Install. length mm
P
rocess connection
RTD temperature probe Data Sheet 90.2006
90.2006/10-390-1003-1-8-250-104/000
90.210-F95
1 x Pt100
max. 300°C
250
Thermocouples Data Sheet 90.1006
901006/45-551-2043-2-xxxx-11-xxxx
2 x NiCr-Ni, Typ
E „K“
max. 1
150°C
50...2000